8. Technical Specifications
Actuator EA ¢1
Rated voltage
Rated voltage tolerance
Rated output
Electric impedance
Altitude
Protection class
Duty cycle
Overload protection
Electrical connections
Control time
Actuating angle
Nominal torque
Peak torque
Ambient temperature
Allowable humidity
5)
Pollutiongrade
Overvoltage-category
Housing materials
Position indicator
Emergency manual override
1)
Overload protection of the motor is dimensioned so that the motor
and the power supply board are protected. As soon as the load is
in the torque range, the actuator runs again.
2)
For temperatures below –10 °C as well as condensation, the
heating element no. 198 ¢90 086 should be built in (see Section 9. 1 ).
3)
Protection rating IP67 for use of cable glands and vertical
installation.
4)
Linear decreasing to 50% relative humidity with 40 °C
5)
Per EN 6¢0¢0-¢
100–230 V, 50/60 Hz
24 V =/24 V, 50/60 Hz
w 10%
22 VA at 24 V AC/DC
40 VA at 100–230 V AC
230V, 100k
24V, 4k7
l 2000m
IP 65 per EN 60529
UL/CSA: Indoor use
40% at 25 °C / ¢5 min
current/time dependent
(resetting)
Connector plug 3 P+E per
DIN EN 175301-803
(formerly DIN 43650)
additional cable entry point
for PG ¢1
5 s / 90° at Mdn
max. 270°, set to 90°
10 Nm
20 Nm
–10° to +45 °C
max. 80% up to 31 °C
2
5)
II
PP fiberglass reinforced,
flame retardant,
external stainless steel screws
optical, integrated
integrated
3)
1)
2)
4)
¥ ‡