FINDING THE DEPTH OF YOUR WELL
The jet tank system installs differently depending on the depth
of your well. Tie a small but heavy weight to the end of a piece
of string (be sure there is enough string; some wells are very
deep). Lower the weight into the well until it reaches the
bottom. Take up the slack and mark the string at ground level.
Pull the weight out of the well and measure from the bottom
of the weight to the ground level mark. This is the depth of
your well. Subtract five feet from the depth of your well. This
number should not exceed the maximum rated depth for your
pump. If it does, it will greatly hinder or prevent the proper
operation of the pump.
115V OR 230V OPERATION
Your pump is equipped with one of two types of dual voltage
motors. Follow the instructions to wire the motor for the
proper voltage. The voltage of the pump must match the
voltage of the power supply.
WIRE SELECTION GUIDE
NAME-
MAX. WIRE LENGTH USING AWG SIZE
VOLTAGE
PLATE
#14
#12
AMPS
115
10.6
118
189
230
5.3
475
756
FUSE AND CIRCUIT
BREAKER SIZE GUIDE
LOW PEAK - CART. TYPE
STANDARD LINE
FUSETRON - CART. TYPE
PLUG FUSE*
FUSTAT - PLUG TYPE*
115V
230V
115V
20
10
12
*For circuits not over 150 volts to ground.
#10
#8
296
464
1184
1857
CIRCUIT BREAKER
230V
115V
230V
6-1/4
20
15
IMPORTANT: SELECT CORRECT VOLTAGE
VOLTAGE SELECTOR
AT REAR OF MOTOR
(USE NEEDLE
NOSE PLIERS)
PULL SELECTOR -
ROTATE - REINSERT
HIGH
LOW
VOLTAGE
VOLTAGE
230
115
WIRING THE PUMP
Remove the cover from the pressure switch. Connect the bare
copper ground to the ground screw in the pressure switch.
Connect the power supply to the terminals marked "Line" in
the diagram below.
LINE
LINE
GROUND
2
GRD
UNGROUNDED
230V
115V
VOLTAGE
SELECTOR
TERMINAL BOARD
USE COPPER CONDUCTORS ONLY
MOTOR
MOTOR
LINE
L1
L2
23833A203