Honeywell F300E Guide D'installation page 14

Electronic air cleaner
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

NOTE: To reduce the risk of electric shock, this product has a grounding type plug that has a third (grounding)
pin. This plug only fits into a grounding type power outlet. If the plug does not fit into the outlet, contact a
qualified electrician to install the proper outlet. Do not change the plug in any way.
Alternatively, the electronic air cleaner can be wired with conduit.
1 INTERLOCK SWITCH.
2 SHORTING BAR FOR OZONE REDUCTION.
3 AIRFLOW SWITCH DISABLE JUMPER, R16.
4 NEON LIGHT.
5 OPTIONAL W8600F AIR CLEANER MONITOR.
6 JUMPER LOCATION FOR IONIZER CURRENT SELECTION.
7 JUMPER LOCATION FOR IONIZER VOLTAGE SELECTION.
1. Open access door.
2. Remove and retain the two screws from the front of the power box and the two screws from the sides of the
power box. See figure on page 13.
3. In the power box, remove and retain two wire nuts that connect the line cord leads to the power box wiring.
4. Remove the wire nut to disconnect the ground choke assembly from the power cord green lead.
5. Remove the power cord and the strain relief.
6. Install the plug (provided with the literature pack) in the hole left by the power cord.
7. Attach conduit through a power box side knockout.
12
P3
BLACK
4
U4
BLACK
2
P4
P8
7
J4
POWER SUPPLY
3
J4
ORANGE
JUMPER
GRAY
VIOLET
BLACK
AIRFLOW SWITCH PLUG, J3.
BLACK COLLECTOR
RED IONIZER
T1
J8
P5
0.25mA
0.9mA
1.05mA
6
1.29mA
1.65mA
2.1mA
BROWN
P2
P1
BLACK
1
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
TEST
BUTTON
RED
CONTACT
BOARD
BLACK
BLACK
GREEN
GROUND
GREEN
F300 Electronic Air Cleaner 68-0240EF—08
CHOKE
M32904