Paramètres De La Tête - RayTek MI3 Serie Manuel D'utilisation

Table des Matières

Publicité

Modbus
15.2.2.2 Paramètres de la tête
<n> ... numéro de la tête en fonction des têtes enregistrées
Starting
Size
Modbus
address
[bits]
Access
<n>005
8
discretes
input
<n>010
64
input register hex
<n>020
64
input register string
<n>030
64
input register string
<n>040
16
input register short
<n>050
32
input register string
<n>060
32
input register float
<n>070
32
input register float
<n>080
32
input register float
<n>090
32
input register float
<n>100
32
holding
register
<n>110
32
holding
register
<n>120
16
holding
register
<n>130
16
holding
register
<n>140
16
holding
register
<n>150
32
holding
register
<n>160
32
input register float
<n>170
32
input register float
<n>180
32
holding
register
<n>190
32
holding
register
<n>200
32
holding
register
<n>210
16
holding
register
104
Data
Content
Type
bit field Head Status
Head serial number
Head identification
Firmware Rev.Head
Head Address
Head special
Device Bottom range
Device High range
Target temperature
internal sensor temp.
float
Ambient background
temp. compensation
float
Advanced hold with
average
short
Control ambient
background temp.
compensation
short
Laser control (only with
laser device)
short
Relay alarm output
control
float
Advanced hold threshold number within range <n>060 .. <n>070 C
Currently calculated
emissivity
Current calculation
setpoint / relay function
float
Sensor Gain
float
Sensor Offset
float
Emissivity internal
short
Presel. Emissivity
Pointer
Rev. G3 Oct 2020
Values
bit0: Temperature Unit
(0: deg. C, 1: deg. F)
bit1: Object temperature out of range
bit2: Ambient temperature out of range
bit3: Parameter error
bit4: Register write error
bit5: Self-test error
bit7: Background temp. compensation
(0: off, 1: on)
e.g. 10C02752
e.g. "MI310LTS"
e.g. 2.10
1 .. 9
e.g. !99HSRAY (read only)
-40 .. 1300 [°C]
-40 .. 1300 [°C]
number within range <n>060 .. <n>070 T
0 .. 999.9 [s]
0: sensor temp.
1: via number
2: via ext. input
0: OFF, 1: ON
0: off
1: Target
2: Ambient
0.1 .. 1.1
number within range <n>060 .. <n>070 CS
0.8 .. 1.2
-200 C .. +200 C
0.1 .. 1.1
0 .. 7
MI3[M]
command
HEC
HN
HI
HV
HA
HS
XB
XH
I
A
AA
AC
HL
KH
CE
DG
DO
E
EP
MI3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mi3commMi3mcommnMi3mcomm

Table des Matières