ENG
6.4.1.2
Cleaning the external heat exchanger (condenser)
ATTENTION
Damage to components
Damage to the heat exchanger fins due to incorrect cleaning.
•
Clean the heat exchanger fins with a soft brush, compressed air or a vacuum cleaner with a brush attachment.
NOTE
The time intervals for cleaning depend strongly on the contamination of the ambient air.
Fig. 28: Cleaning the heat exchangers and fans
Prerequisites
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
•
The unit cover and front flap are removed, see chapter "Removing the front flap and unit cover", Page 55.
Required tools and materials
•
Soft brush
•
Vacuum cleaner with brush attachment or compressed air cleaner
•
Fin comb
Operating Manual | Roof-mounted Cooling Unit | Standard Controller (SC) – 115 V | 086100026b
G00049