Caution :
This device must be installed by a suitably
qualified electrician according to the
installation's standards.
Product description and operating
principles
Occupancy sensors EE816 are presence
detectors designed to detect low level
movements (movements from body or arms).
Detection is by means of a pyroelectric
IRsensor located under the detection lens.
The occupancy sensor measures the
brightness in the room on a continuous basis
and compares it to the level preset on the
1
potentiometer
(or by means of the remote
control EE807).
Settings
The Lux threshold and time out period can be
set with the potentiometers or by using the
installer remote control (EE807).
Test Mode
This mode makes it possible to validate the
detection area. To select this mode, set the
1
potentiometer
to the position "auto test".
The green or red LED behind the lens is on for
2 seconds after detection.
The red LED indicates that the light level
measured is lower than current setting.
If the green LED is on, the light level measured
is higher than current setting.
There is a time out of 2 minutes which is
reactivated after each detection.
The output is also switched during 2s. after
each detection.
It is also possible to use the remote control
EE807 to set the detector in test mode if the
potentiometer is set on "auto test".
Functional modes
The detector has 2 different modes.
- automatic (presence detection).
- semi-automatic (absence detection).
The power up and cell operation can be set for
each mode.
Action
Settings
Use Auto settings
Auto Settings
(factory) or set by
Put the Lux potentiometer on "auto test".
the remote control
The settings are predefined :
to switch the light
Lux = 400,
automatically for a
time = 20 min,
defined time.
: test mode for 2 min.
Remote control settings EE807
(manual settings inhibited).
Automatically switch
Installer settings
on the light for a
defined time.
Test and validate the
Test mode
detection zone.
Move the potentiometer
On this position, the remote control EE807
can be used.
4
Automatic mode (presence detection)
In this mode the light is controlled by motion in the
detection area and ambient light levels.
If presence is detected whilst the light levels are
below the required Lux level, the sensor is activated
and regulates the light whilst there is still
occupancy and for the time out period afterwards.
Once the sensor has deactivated the lights, it will
require new occupancy whilst the ambient light
levels are below the required Lux level to activate
the lights again.
This mode can be changed via the IR remote
control EE807 (default mode is presence
detection : automatic).
Lighting time delay is restarted after each detection.
Semi automatic mode ( absence detection)
The sensor needs to be activated by a pushbutton
or a user remote control input.
Once the sensor is activated, it will regulate the
lights whilst there is still occupancy and for the time
out period afterwards.
Once the sensor has deactivated the lights, it will
require another input from the wallswitch or the
remote control to switch the lights on.
Power Up
A parameter of the detector allows the choice of
state for the lighting after power up (mains return).
During warm up phase, the green or red LED blinks.
In the Power up ON state the lighting will
automatically be energised when mains power is
initially supplied or returned to the sensor.
In the Power up OFF state the lighting will not
be energised and the sensor will not operate during
warm up period.
This parameter is modified using the installer
remote control EE807.
POWER UP state :
• ON : The light is immediately switched on for 30s.
after power up.
The detector switches to the according mode
after the warm up. In case of detection, the light
(in automatic mode) remains on during the time
delay; otherwise the light is switched off.
• OFF : The detector switches to the selected mode
after warm up.
DALI/ DSI recognition
The green LED blinks for this period if a DALI load
is recognised.
The red LED blinks continuously in case of DALI
bus error (unplugged wiring, ...) or DSI load.
Potentiometer
auto
test
1
on
auto
test
1
on
1 min
20 min
1 h
auto
to "auto test".
test
1
on
Lighting regulation modes
In association with Digital Regulating Ballasts
(DALI and DSI), these products offer lighting
control functions.
The used protocol is automatically recognised.
Adjustment potentiometers are used to select
the operating mode of the occupancy sensor.
• Mode 1 : regulation active in auto mode
• Mode 2 : regulation active with local set point
• Mode 3 : regulation not active.
Mode 1
regulation
active
auto
test
Mode 1 : regulation active in automatic mode.
After detection, the DALI output controls the
lighting level according to the value set, using
the pushbutton input or the remote control.
This value is memorised as the new setpoint.
The default set point is 400 lux.
The output is controlled for the time set by the
potentiometer
Mode 2 : regulation active with local set point
(potentiometer).
After detection, the DALI output controls the
lighting level according to the value set by the
potentiometer
This level can be temporarily adjusted via a
pushbutton. The light level is fixed.
The output is controlled for the time set by the
potentiometer
Mode 3 : regulation inactive
During presence detection, the detector
controls its output at a preset level (100% by
default), which can be modified by a
pushbutton. The new instructions are saved.
The output is controlled for the length of time
set by the potentiometer
At the end of this time delay, the output is set
to a minimum level for 15 min. and is then
switched off.
Use of override input
A connected pushbutton can be used to
modify the state of the output.
Short presses override the state of output for
the time period set by the potentiometer
Long presses are used to modify the level of
the set point.
Technical features
Electrical characteristics
Supply voltage : 230 V
Consumption with no load : 60 mW
DALI/DSI output capacity : 24 ballasts
lux
Functional characteristics
2
Lighting output operating time : 1min.—> 1h
Brightness level : 5 —> 1000 Lux
Recommended installation height : 2,5—> 3,5m
Detection range : Ø 7m
(installed product height : 2.5m)
Hole size required : 60mm
Environment
Operating temperature : -10 °C —> +45 °C
Storage temperature : -20 °C —> +60 °C
Class of insulation : II
lux
IK 03
Index of protection : IP41
2
Fire resistance : 650°C
Standards : IEC 60669-1, IEC 60669-2-1
Connection capacity :
0.5mm
0.5mm
auto
test
1
lux
lux
2
2
on
Mode 2
Mode 3
regulation
regulation
active
inactive
auto
auto
test
test
1
1
lux
x
lux
2
2
on
on
2
.
1
or the remote control.
2
.
2
.
+10% -15% 50-60 Hz
2
2
to 1.5mm
flexible,
2
2
to 1.5mm
rigid
1
lux
2
on
2
.
6E 7606.d