Battery operation
Applied load in percentage
Approximate autonomy in minutes with
charged batteries
Recharge time up to 90% of total load
Technical data and quantity of batteries
Reserve signal
Minimum voltage for battery operation
Average battery life
Bypass Specifications
Type of bypass
Standards
Safety
Electromagnetic compatibility:
Immunity - emission
Performance and features
All manuals and user guides at all-guides.com
Whad 1500
50 %
27
5-6 hours according to level of discharge
N° 6 pcs 12V 7Ah sealed
lead-acid, maintenance free maintenance free batteries connected in
connected in series
From 32.2V to 36V can be programmed by operator
From 27V to 31.5V with automatic selection according to
load or can be programmed by operator
3-6 years according to use and working temperature
The batteries in the UPS are subject to a reduction in
capacity according to their age (a feature of lead batteries
declared by their manufacturer in the technical manual). For
example, the reduction in the capacity of a 4-year-old battery
can reach 40% with a proportional reduction of autonomy
times of the UPS when operating in battery mode.
19
8-04-2008
9:52
Whad 2000
80 %
50 %
80 %
15
22
10
N° 3 pcs 12V 7Ah, sealed, lead-acid,
series for each powerboard
Warning !
Electro-mechanical
Conforms to standard EN 62040-1-1
Conforms to standard EN 50091-2
Conforms to standard EN 62040-3
Pagina 19
Whad 2500
50 %
80 %
16
8