Cartridge Replacement and Calibration
Remote Calibration
The Calibration screen contains four (4) lines of information:
Line 1:
Indicates the mode (Calib), the device address for calibration
and the type of device to calibrate (301W)
Line 2:
Indicates the status (Normal or In Calib...) of the specified
device
Line 3:
Displays the function to perfom (Set Zero)
Line 4:
Displays the function to perform (Set Span) and the
calibration concentration (246 PPM)
1. On the first line, scroll to the device address and press Enter
2. Scroll through the devices to display the desired device* and press
Enter to select.
3. The second line displays the device's status
4. Scroll to select the desired function, Set Zero to set the device's
zero
5. Upon selecting Set Zero, the controller requests confirmation.Pres
Enter to confirm or Esc to cancel. If confirmed, the controller sets
the 301W's zero. This takes only a few moments and returns to the
default calibration screen.
Note: Never calibrate the sensor zero with ambiant air only. Always
use Nitrogen (N
* The device must be configured in the 301CW's database in order to
be included in the device addresses displayed on screen.
30