• Maximum speed can be activated using fast button. When preset maximum fan speed (boost) time is over,
previous speed is automatically restored;
• 0..10 VDC CO
sensor can be connected for activation of maximum speed based on the given CO
2
Temperature
• Temperature from 15 to 30 C may be set by remote controller. Note: Temperature of MCB controller can be
adjusted from 0 up to 40C (it depends on MCB settings).
• Supply air and set temperatures can be displayed interchangeably (set temperature is displayed for 5 seconds,
then supply air temperature is displayed for 2 seconds)
Remote control (Modbus)
Controller supports fully configurable Modbus interface. Panel can operate as master and slave device in mod-
bus network and also it can be fully controlled and configured not only via service menu but also via modbus
interface.
User menu
In order to reach user menu, press down B2 and B3 for 3 seconds.
In user menu, menu items (P.01, P.02 etc.) settings are displayed sequentially. Menu item is selected using ele-
ments B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using elements
B4 and B6. Press B5 to save the parameter and to return to menu.
Due to limitations of segment display, values of P.04 and P.05 are shown divided by 10, i.e. if 20 is displayed, it
means that real value is 20 x 10 = 200.
.06 - Filter timer resets by pressing B2 and B3 for more than 5 seconds. Filter timer also resets by clearing
fault signal.
Touch element B1 to exit menu.
No.
.01
.02
Supply air temperature display
.03
.04
.05
.06

Intended use

1) Modbus master (main)
This controller can control other devices (controlled by MODBUS protocol) for example, air handling units. This
can be set in service menu by selecting required parameters for service menu items F.17, F.18, F.19, F.20, F.21.
To control not only standard devices, select "CUSTOM" in menu item F.20 and device addresses in menu items
from F.22 up to F.37. If devices have no such addresses, in fields of given menu items enter "00:00". Normally,
this controller is used with ECO or PRV control boards.
www.salda.lt
All manuals and user guides at all-guides.com
Name Possible values
Sleep mode
Sound
CO
required (ppm) 0 – 99 x 10 ppm
2
CO
allowed difference 0 – 99 x 10 ppm
2
Filtrer timer
CONTROLLER
(master)
0 - Off
1 - 99 sleeping time in seconds
0: Off
1: 1 – 9 sound tone
0: Not shown
1: Shown interchangeably with the set temp
Displaying number of days from the last
change of the filters
MODBUS
AHU
(slave)
parameters.
2
Default
value
0
2
0
20 x 10
5 x 10
0
47

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

P0084 aa 0005

Table des Matières