6. Electrical work

6.1. Caution
1 Follow ordinance of your governmental organization for technical standard
related to electrical equipment, wiring regulations and guidance of each electric
power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm
[2 inch] or more) apart from power source wiring so that it is not influenced by
electric noise from power source wiring. (Do not insert transmission line and
power source wire in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor
units, because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor trans-
mitting and receiving will cause erroneous operations.
C
L1 L2 GR
M1
M2
S
M1
M2
S
TB1
TB3
TB7
A
B
ø24 knock-out hole
(For transmission wires)
A Power source
C Screw on the electrical component box for ground connection (TB3)
B Transmission line
D Screw on the electrical component box for ground connection (TB7)
Fig. 6-1

6.3. Wiring transmission cables

1 Types of control cables
1. Wiring transmission cables
Kind of transmission cable
Shielding wire (2-core) CVVS, CPEVS or MVVS
Cable diameter
More than 1.25 mm
Maximum wiring length
Within 200 m [656 ft]
2. M-NET Remote control cables
Kind of remote control cable
Shielding wire (2-core) CVVS, CPEVS or MVVS
Cable diameter
0.5 to 1.25 mm
When the wiring length exceeds 10 m [32 ft], use
Remarks
cable with the same specifications as transmis-
sion line wiring.
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are necessary.)
<Examples of Transmission Cable Wiring>
I M-NET Remote Controller (Fig. 6-2)
I MA Remote Controller (Fig. 6-3)
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. The jumper connector CN41 on the control panel does not change.
f.
Connect the terminal S on the terminal block for central control for the power supply unit to the ground terminal (
g. Set the address setting switch as follows.
Unit
Range
IC (Main)
01 to 50
IC (Sub)
01 to 50
OC
51 to 100
M-NET R/C (Main)
101 to 150
M-NET R/C (Sub)
151 to 200
MA R/C
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
D
CONDUIT PLATE:
accessory
ø37 knock-out hole
(For power supply wires)
CONDUIT WASHER:
accessory
[AWG 16]
2
[AWG 20 to AWG 16]
2
Use the most recent address within the same group of indoor units
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in
sequence with the IC (Main)
Use the most recent address of all the indoor units plus 50
* The address automatically becomes "100" if it is set as "01 - 50".
Set at an IC (Main) address within the same group plus 100
Set at an IC (Main) address within the same group plus 150
Unnecessary address setting (Necessary main/sub setting)
7 Only the transmission line specified should be connected to the terminal block
for outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for
transmission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.
8 In case to connect with the upper class controller or to conduct group operation
in different refrigerant systems, the control line for transmission is required
between the outdoor units each other.
Connect this control line between the terminal blocks for centralized control.
(2-wire line with no polarity)
When conducting group operation in different refrigerant systems without con-
necting to the upper class controller, replace the insertion of the short circuit
connector from CN41 of one outdoor unit to CN40.
9 Before turning outdoor unit on, be sure to turn the indoor units on.
6.2. Control box and connecting position of wiring
(Fig. 6-1)
1. Connect the wiring between the outdoor unit and the indoor unit to the trans-
mission terminal block (TB3) of the outdoor unit.
Connect the wiring between the outdoor unit and the centralized control system
to the transmission terminal block (TB7) of the outdoor unit.
When using shielded wiring, connect the ground of the shielded wiring to the
shield terminal (S) of the terminal block (TB3) or (TB7).
If the connection of the outdoor unit's transmission power supply connector
has been changed from CN41 to CN42, connect the shield terminal (S) of the
terminal block (TB7) to the screw (D) using the included lead wire.
* The shield (S) terminal of the transmission terminal block (TB3) is connected to
the ground (C) when the unit is shipped from the factory.
2. Conduit mounting plates are being provided. Remove the knock-out pieces
from the piping cover, pass the power supply and transmission wires through
the appropriate knock-out holes, and connect the wires to the terminal block.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
3. MA Remote control cables
Kind of remote control cable
Cable diameter
Remarks
* Connected with simple remote controller.
2 Wiring examples
• Controller name, symbol and allowable number of controllers.
Name
Symbol
Outdoor unit controller
OC
PUMY-P36NKMU3
PUMY-HP36NKMU1
Indoor unit controller
IC
PUMY-P48NKMU3
PUMY-HP48NKMU1
PUMY-P60NKMU3
Remote controller
RC
) in the electrical component box.
Setting Method
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
[AWG 22 to AWG 16] (0.75
2
to 1.25 mm
[AWG 18 to AWG 16])*
2
Within 200 m [656 ft]
Allowable number of controllers
1 to 11 units per 1 OC
1 to 12 units per 1 OC
MA
Maximum of 2 per group
en
10