- To disable the alarm buzzer, press this button for a second. Each time a new alarm
event is encountered and the alarm sounds, press this button to turn it off.
NB: If unable to disable the alarm buzzer, the cause may be any of the following:
Low Battery, Overload, Fan Failed, Fan Fault Time Out, Over Temperature.
3. Configure:
To reconfigure the internal UPS setup options, follow the procedure as below:
Step 1: Press the Configure
will transfer from configure mode to "output voltage mode".
Step 2: Press the Configure
allows you to select the "output voltage mode" one by one.
Step 3: After selecting the mode, press the Enter
seconds, the "output voltage mode" is configured.
Step 4: UPS will automatically transfer from configure mode to "operating mode".
Step 5: Press the Configure
you to select the "operating mode" one by one.
Step 6: After selecting the mode, press the
the "operating mode" is configured.
4. Enter:
Press the
button after you choose the mode.
5. Input Type (Operating Mode) LED:
Normal mode: The Yellow LED indicator will be on during normal mode, the UPS
accepts AC input voltage range from +/-20%.
Generator: No change to voltage window. However, the low frequency transfer point is
changed to 40Hz and there is no limitation for the high frequency transfer point.
Wide range: The LED indicator will come on, the UPS accepts AC input voltage range
from -30% ~ +20%.
6. Voltage Range (Output Voltage Mode) LED:
UPS Output voltages selection: 110VAC/120VAC/127VAC or 220VAC/230VAC/240VAC.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière – 44700 Orvault – FRANCE - www.infosec.fr
Hot Line : tel : + 33 (0)2 40 76 15 82 - fax : + 33 (0)2 40 94 29 51 - hotline@infosec.fr - 09 05 04 205 12
All manuals and user guides at all-guides.com
button for more than three seconds. Then the UPS
button for more than one second, the UPS
button for more than one second; the UPS will allow
button for more than three
button for more than three seconds,
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E3 750 vaE3 1000 vaE3 1500 vaE3 2000 vaE3 3000 va

Table des Matières