[Fig. 7.2.1]
Max. 20m [65 ft]
1.5-2 m [5 to 7 ft]
B
A
K
B
D
E
F
F
H
[Fig. 7.2.2]
K
J
F
A
B
35
[1-13/32]
25 [1]
C
D E
I
A Indoor unit
B Insulation (long) (accessory)
C Tie (long) (accessory)
D Visible part
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in.] PVC, field supplied)
H Insulation (field supplied)
I Tie (short) (accessory)
J Max.180 ± 5 mm [7-3/32 ± 7/32 in.]
K The joint of the insulation must be positioned up.
[Fig. 7.3.1]
A
B
E
F
D
A Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in.].
B Remove the water supply port.
C About 2 L
D Water
E Filling port
F Screw
4
All manuals and user guides at all-guides.com
Max. 300 mm [11-13/16 in.]
C
F
L
M
D
D
F
G
I
(Unit: mm [in.])
G
H
25 [1]
E
[Fig. 7.3.2]
C
7.2
Correct piping
Wrong piping
A Insulation (9 mm [3/8 in.] or more)
B Decline (1/100 or more)
N
B
C Support metal
J
K Air release tube
L Trap
M Odor trap
O
Drain pipe system
D O. D. ø32 mm [1-1/4 in.] PVC TUBE
E Make it as large as possible. About 10 cm [3-15/16 in.].
F Indoor unit
G Make the piping size large for drain pipe system.
H Decline (1/100 or more)
I O. D. ø38 mm [1-1/2 in.] PVC TUBE for drain pipe system.
(9 mm [3/8 in.] or more insulation)
J Up to 550 mm [21-21/32 in.]
N Drain hose (accessory)
O Horizontal or slightly upgradient
[Fig. 7.2.3]
I
B
A
5
[7/32]
D
A Indoor unit
B Insulation (short) (accessory)
C Tie (short) (accessory)
D Attaching the band
E Insertion margin
F Drain hose (accessory)
G Drain pipe (O.D. ø32 mm [1-1/4 in.] PVC, field supplied)
H Insulation (field supplied)
I Max.145 ± 5 mm [5-23/32 ± 7/32 in.]
7.3
<Indoor controller board>
(Unit: mm [in.])
G
F
25 [1]
H
E
C
SWE