6. FONCTIONNEMENT GÉNÉRAL DU COFFRET
ALLUMAGE DU
COFFRET
PRÉSENCE RÉSEAU
LA VALEUR DE TENSION MESURÉE EST EN DEHORS DU SEUIL ADMIS
PHASE MANQUANTE OU SÉQUENCE ERRONÉE
INDIQUE QUE LE MOTEUR EST EN MARCHE
INDIQUE QUE LE MOTEUR EST ÉTEINT
INDIQUE UNE ALARME DE SURCHARGE DU MOTEUR QUI PROVOQUE L'ARRÊT
FONCTIONNEMENT MANUEL: EST ACTIVÉ À PARTIR DE L'ÉTAT STOP EN MAINTENANT LE BOUTON APPUYÉ
DANS CETTE CONDITION, LE COFFRET DÉMARRE LE MOTEUR JUSQU'À CE QUE LE BOUTON SOIT RELÂCHÉ
EN EXCLUANT LE CONTRÔLE SUR L'AUTOMATIQUE. EN RELÂCHANT LE BOUTON, VOUS POUVEZ RETOURNER
À L'ÉTAT STOP
FONCTIONNEMENT AUTOMATIQUE: EST ACTIVÉ À PARTIR DE L'ÉTAT STOP EN APPUYANT SUR LE BOUTON.
DANS CETTE CONDITION, LE COFFRET FONCTIONNERA SELON L'APPLICATION FIXÉE
FONCTIONNEMENT STOP: DANS CETTE CONDITION, LE COFFRET NE DÉMARRE PAS LE MOTEUR
N.B.: TOUTES LES ALARMES SONT AUTOMATIQUEMENT RÉINITIALISÉES À L'EXCEPTION DE LA SURINTENSITÉ
DU MOTEUR QUI EST RÉINITIALISÉE EN APPUYANT SUR LE BOUTON PENDANT 2s
VIDANGE
FLOTTEUR MAX 2 ON, LE MOTEUR EST ACTIVÉ
MANQUE D'EAU (NIVEAU MINIMUM DÉCOUVERT), LE MOTEUR EST DÉSACTIVÉ
ATTENTE REMPLISSAGE, LE MOTEUR EST DÉSACTIVÉ
N.B.: LE MOTEUR NE DÉMARRE QUE S'IL EST EN FONCTIONNEMENT AUTOMATIQUE ET NE S'ARRÊTE QUE LORSQUE
LE FLOTTEUR MAX 2 EST OFF OU LE FLOTTEUR MIN EST OFF
REMPLISSAGE
FLOTTEUR MAX 2 ON, LE MOTEUR EST ACTIVÉ
MANQUE D'EAU (NIVEAU MINIMUM DÉCOUVERT), LE MOTEUR EST ACTIVÉ
ATTENTE REMPLISSAGE, LE MOTEUR EST ACTIVÉ
N.B.: LE MOTEUR NE DÉMARRE QUE S'IL EST EN FONCTIONNEMENT AUTOMATIQUE ET NE S'ARRÊTE QUE LORSQUE
LE FLOTTEUR MAX 2 EST OFF OU LE FLOTTEUR MIN ET MAX1 SONT OFF
LEGENDE
Éteint
LED
ON
ATTENTE 10s
Allumé
8
Clignotant
Clignotant rapide
<0,5s