DESCRIPTION AFTER-HEATER CONNECTION
Available types:
Article code
5997460
5997461
5997462
Installation of a after-heater on an ERV
1. Secure the heater in the outgoing airflow from the ERV (Supply)
2. Note the direction of airflow, indicated by an arrow on the heater.
3. Position the heater as shown in the icons below:
(electrical connection box downwards not allowed due to operation maximum thermostat)
4. Place the supplied temperature sensor after the heater in the duct in the air flow.
Distance: 3 times the pipe diameter. Place the probe in the center of the tube.
28
Capacity
Power consumption
1 kW
4.4 A
2 kW
8.8 A
3 kW
13.2 A
Tube diameter
Min. airflow
Ø 200 mm
170 m
Ø 250 mm
270 m
Ø 350 mm
520 m
/h
3
/h
3
/h
3