FloPro
-MD - Installation and Operation
™
2 . Review all the values on the screen and tap the check mark icon to save displayed settings
to the FloPro-MD .
• MEASURED GAS
o Tap NG to set your FloPro-MD to measure Natural Gas .
o Tap LPG to set your FloPro-MD to measure Propane .
• BTU/CU FOOT
o By default, the FloPro records BTU calculations with a default value of 1000 for
Natural Gas and 2500 for Propane .
o Tap the default value and use the keyboard to enter a custom value to be used
for BTU calculations in the app and in data exports .
• DATA SAMPLE RATE
o Selecting a data sample rate of 1 Second will record the average value once per
second for a period of up to 12 hours .
o Selecting a data sample rate of 1 Minute will record the average, minimum, and
maximum values every 1 minute, for a period of up to 3 days .
o Selecting a data sample rate of 10 Minutes will record the average, minimum,
and maximum values every 10 minutes, for a period of up to 30 days .
3 . Save settings . After making the required changes in Settings, tap the check mark in the top
left of the screen .
4 . Select Delete Stored Data to erase existing data from the device . Use this option only if
you are sure you want to ERASE ALL DEVICE HISTORY LOGS .
FloPro
-MD Installation and Operation Manual
™
9