Configuration errors (BLINKING SYMBOLS)
7 SEGMENTS DISPLAY
SYMBOL
2
N.B.: For the meaning of the number that is displayed in case of a malfunction, please refer to
the "TROUBLESHOOTING" paragraph in this manual.
On the emitter of the Multibeam models, near each beam, is present a red LED which
permits an easy detection of the beam.
TEST FUNCTION
By means of the test function, which simulates occupation of the protected area, it is
possible to verify the operation of the entire system by means of an external supervisor
(e.g. SPS, control module, etc.).
The SLC / SLG 410 RF light curtain / light grid system features an automatic self-diagnosis
function that enables it to detect response time malfunctions (this time is declared for each
model).
This safety system is permanently active and does not require any interventions from the
outside. The TEST function is available should the user wish to check equipment connected
downstream of the light curtain / light grid (without physically entering the protected area).
By means of this function the OSSDs can be switched from ON to OFF as long as the
function remains active. Please see table 2 (page 12) for details about the use of the test
function.
The minimum duration of the TEST function must be 40 msec.
MEANING
OSSD erroneously
connectedt o 24VDC
LED
RED (2)
GREEN (3)
ON
OFF
YELLOW (1)
OFF