CONFIGURATION AND OPERATION MODES
The SLC / SLG 410 RF operation mode is selected realizing appropriate connections on the
M12 8 poles of the Receiver (Table 6 and Table 7).
AUTOMATIC MODE
The SLC / SLG 410 RF light curtain does not dispose of a start/restart interlock
circuit in automatic mode. In most applications this safety function is necessary.
Please consider the risk-analysis of your application about this matter.
In AUTOMATIC mode, the two static outputs OSSD1 and OSSD2 follow the status of the
guarded opening.
SEL_A (PIN 5)
connected to :
OSSD1 (PIN 1)
SEL_A (PIN 5)
connected to :
OSSD2 (PIN 3)
MANUAL MODE
Use of manual mode (start/restart interlock activated) is compulsory if the safety
device controls an opening to protect a danger area and a person, after passing
through the opening, may remain in the danger area without being detected (use as
'trip device' according to IEC 61496). Failure to comply with this rule may result in
very serious hazards for the persons exposed.
In this operating mode the safety outputs OSSD1 and OSSD2 are activated (+24VDC) only if
the protected area is free and after the reception of the RESTART signal, using a push
button or thank to an appropriate control on the SEL_A or SEL_B input (ref. Table 7).
After an interception of the protected area, the safety outputs will be de-activated.
To re-activate them it will be necessary to repeat the sequence described above.
The RESTART command is active with a voltage of +24VDC.
The minimum duration of the RESTART command is 400ms.
SEL_A (PIN 5)
connected to :
24VDC (PIN 2)
SEL_A (PIN 5)
connected to :
24VDC (PIN 2)
(through the RESTART
pushbutton)
18
with the area guarded clear, the outputs will supply +24VDC
with the area occupied they will supply 0VDC.
CONNECTION
SEL_B (PIN 6)
connected to :
OSSD2 (PIN 3)
SEL_B (PIN 6)
connected to :
OSSD1 (PIN 1)
CONNECTION
SEL_B (PIN 6)
connected to :
24VDC (PIN 2)
(through the RESTART
pushbutton)
SEL_B (PIN 6)
connected to :
24VDC (PIN 2)
K1_K2 (PIN 4)
connected to :
0VDC
K1_K2 (PIN 4)
connected to :
24VDC
(through series of contatcts
N.C. of external relays)
Table 6
K1_K2 (PIN 4)
connected to :
0VDC
K1_K2 (PIN 4)
connected to : 24VDC
(through series of contatcts
N.C. of external relays)
Table 7
OPERATION MODE
AUTOMATIC without
K1-K2 feedback control
AUTOMATIC with
K1-K2 feedback control
OPERATION MODE
MANUAL without K1-K2
feedback control
MANUAL with
K1-K2 feedback control