ADJUSTING THE FLOW RATE
Ceramic cartridge Ø40:
Flow rate limited to 5 lpm at 3 bar.
Ceramic cartridge Ø40 with EP pressure balancing: (see operation principles (fig. E)).
Flow rate limited to 5 lpm at 3 bar.
TEMPERATURE ADJUSTMENT
Temperature limiter:
• All BIOCLIP mixers are fitted with the maximum temperature limiter pre-set at the factory.
For the UK and Ireland we recommend installing an appropriate, approved thermostatic mixing valve
(TMV) to provide safe, anti-scald hot water where a high risk of scalding has been identified.
Where thermostatic mixing valves are installed the temperature limiter MUST BE REMOVED from
all point-of-use mixers.
• Recommended maximum temperature settings for UK healthcare applications are: bidets 38°C,
washbasins and showers 41°C. For all other countries please refer to the relevant hot water safety
guidelines.
Adjusting the mixed water limiter:
• To adjust the pre-set maximum temperature, unclip and reposition the index ring located beneath
the control lever. The position of the index ring will limit the water temperature at the mixer outlet.
• To access the cartridge (fig. C), remove the control lever by removing the cover cap a, unscrew
the grub screw  using a 2.5mm Allen key, and unscrew the collar  from the mixer body.
• To change the hot water (HW) setting (fig. F-1), unclip the index ring a and turn clockwise to lower
the temperature, or anti-clockwise to increase it. Replace the index ring and check the temperature
at the mixer outlet to achieve the desired maximum temperature.
• To return to the maximum hot water position (fig. F-2), align the marker on the index ring 
with the marker on the cartridge .
MAINTENANCE & CLEANING
• Cleaning chrome and stainless steel: do not use abrasive, chlorine or any other acid-based
cleaning products. Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap/valve several times to drain any
remaining water. In the event of prolonged exposure to frost, we recommend taking the mechanisms
apart and storing them indoors.
For the UK market only: Tel. 01491 821 821 - email: technical@delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: sav@delabie.fr
After Sales Care Support:
The installation guide is available on: www.delabie.co.uk