Télécharger Imprimer la page

Honeywell VH2 Données Techniques page 23

Publicité

Les langues disponibles

Les langues disponibles

VH2, VH3, VH4, VH5, VH6, VH7, VH8 ANSI 150 CLASS HIGH PERFORMANCE BUTTERFLY VALVES
24 VAC Transformer
3
Line
Blk
Volts
Red
(–)
Wht
2 to 10 VDC
Feedback Signal (+)
Org
a
Function
Max
100%
On/Off
FC
A – AB = 0%
A – AB = 100%
POP
CCW
CW
CCW
On/Off
24V AC/DC
24 VAC Transformer
18
Line
Commo n
(1)
Volts
Hot
(2)
(3)
Y Input
8
(–)
2 to 10 VDC
(5)
U Output 2 to 10V
(+)
Feedback Signal
Direction of rotation switch
A
Floating Point
FO
POP
CW
FC
A – AB = 0%
0. 5
3
4
0. 1
a
b
CCW
(Y1)
(Y2)
––
Floating Point
24V AC/DC
Fig. 18. Wiring for MBE6...R actuators.
2
10
18
Blk (1) – Common
Red (2) + Hot
A
Wht (3) Y
Input
1
B
12
9
Org (5) U Output 2 to 10V
CCW
CCW
CW
CW
18
18
B
A
B
FO
A – AB = 100%
Y1
Y1
Y2
Y2
POP
0. 5
POP
0. 9
0. 1
0. 9
CW
CCW
CW
––
23
Notes:
Meets cULus requirements without the need of an
electrical ground connection
Actuators may be connected in parallel. Power
2
consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
3
Control signal may be pulsed from either the Hot
8
(Source) or Common (Sink) 24 VAC line.
Contact closures A & B also can be triacs. A & B should
both be closed for the triac source and open for triac
9
sink.
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the
controller. Position feedback cannot be used with a triac
10
sink controller. The actuator internal common reference
is not compatible.
IN4004 or IN4007 diode. (IN4007 supplied)
12
Actuators with plenum rated cable do not have numbers
18
on wires; use color codes instead.
31-00191EF—02

Publicité

loading