Number
Message
60132
RS-485 communica-
tion alarm.
60142
Battery undervol-
tage.
60145
Wrong polarity on
DC terminal detec-
ted.
60150
Battery voltage over
threshold setting.
60168
Ambient tempera-
ture over allowed
range.
60186
Ambient tempera-
ture under allowed
range.
60192
Fan defective or
stuck.
60200
Precharge condi-
tions could not be
met.
60201
Attached load on
DC link can not be
handled.
60202
DC link could not
be charged
60700
Auxiliary supply
overvoltage.
60703
Auxiliary supply
undervoltage.
Messages d'alarme
Messages d'avertissement
Number
Message
10016
Powerfail of 24 V auxiliarysupply has been detected
11000
battery voltage < minimum reference or battery voltage > maximum
reference
Messages d'avertissement
A67-0147-00.BKfr-0
01-01
Effect
No operation pos-
sible.
No operation pos-
sible.
Risk of damaging
hardware.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
Risk of damaging
hardware.
Unstable system.
2022-06-22
Cause
Action
Communication pro-
Check RS-485 com-
blem on RS-485
munication.
bus.
Battery voltage too
Check battery vol-
low.
tage.
Wrong polarity on
Check battery pola-
battery detected.
rity.
Battery voltage over
Change battery
threshold setting.
threshold setting.
Ambient tempera-
Check the ambient
ture over allowed
temperature.
range.
Ambient tempera-
Check the ambient
ture under allowed
temperature.
range.
Fan is defective or
Check fan.
stuck.
Precharge condi-
Check droop-mode
tions could not be
settings, DC link
met.
and battery voltage.
Attached load on
Reduce DC link
DC link can not be
load or change pre-
handled.
charge procedure.
DC link could not
Check DC link and
be charged
connected compo-
nents.
Auxiliary supply vol-
Check the external
tage too high.
24-V auxiliary sup-
ply.
Auxiliary supply vol-
Check the external
tage too low.
24-V auxiliary sup-
ply.
Recherche des erreurs
Detec-
ted by
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
Tab. 29
Caused by
System control
DC-DC module
Tab. 30
89