Messages d'alarme
Number
Message
40300
RS-485 communica-
tion alarm.
40301
RS-485 communica-
tion alarm.
40302
Active interface
(Modbus or Web-
GUI) communica-
tion timeout has
occured
40303
RS-485 communica-
tion alarm.
40304
No slave module
was found, please
check RS-485 con-
nection(s).
40305
Number of or combi-
nation of connected
slave types not sup-
ported.
40412
Software versions
of system control
and module(s) do
not match.
40413
Software versions
of system control
and module(s) do
not match.
40414
Software versions
of system control
and module(s) do
not match.
40415
Software versions
of system control
and module(s) do
not match.
40416
Software versions
of system control
and module(s) do
not match.
60090
Battery overvoltage.
60093
DC link overvoltage.
60102
DC link voltage too
low for operation.
60129
Battery voltage
under threshold sett-
ing.
88
Recherche des erreurs
Effect
Cause
No operation pos-
Communication pro-
sible.
blem on RS-485
bus.
No operation pos-
Communication pro-
sible.
blem on RS-485
bus.
No operation pos-
Active interface
sible.
(Modbus or Web-
GUI) communica-
tion timeout has
occured
No operation pos-
Communication pro-
sible.
blem on RS-485
bus.
System cannot
No slave module
finish start-up proce-
was found.
dure
System cannot
Number of or combi-
finish start-up proce-
nation of connected
dure
slave types not sup-
ported.
System cannot
Software versions
finish start-up proce-
of system control
dure
and module(s) do
not match.
System cannot
Software versions
finish start-up proce-
of system control
dure
and module(s) do
not match.
System cannot
Software versions
finish start-up proce-
of system control
dure
and module(s) do
not match.
System cannot
Software versions
finish start-up proce-
of system control
dure
and module(s) do
not match.
System cannot
Software versions
finish start-up proce-
of system control
dure
and module(s) do
not match.
No operation pos-
Battery voltage too
sible.
high.
No operation pos-
DC link voltage too
sible.
high.
No operation pos-
DC link voltage too
sible.
low.
No operation pos-
Battery voltage
sible.
under threshold sett-
ing.
Action
Check RS-485 com-
munication.
Check RS-485 com-
munication.
Check active inter-
face (Modbus or
WebGUI) or disable
timeout.
Check RS-485 com-
munication.
Check RS-485 con-
nection(s) and
modules.
Check module confi-
guration. Only
homogeneous
modules are allo-
wed on one
RS-485 bus.
Software update
necessary.
Software update
necessary.
Software update
necessary.
Software update
necessary.
Software update
necessary.
Check battery vol-
tage.
Check DC link.
Check DC link pre-
charge.
Change battery
threshold setting.
2022-06-22
A67-0147-00.BKfr-0
Detec-
ted by
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
01-01