I N S TA L L AT I O N
I N S TA L L AT I O N
Overview of Third-Party Controls
The class 2 control input/output compartment enables interface with numerous devices. Choose the
appropriate terminals based upon your application.
Sections include:
Analog I/O
This section contains four ports. Each port can be configured independently to be any of the following
control types. Refer to applicable protocol wiring diagrams.
•
Contact closure input
•
Contact closure output
•
0-10 V input
•
0-10 V output
•
0-24 V input
DMX
"DMX Out" can be configured to operate as a stand-alone DMX universe of control. Refer to applicable
protocol wiring diagrams.
C O N N E C T T H I R D - PA R T Y C O N T R O L S
1.
Use conduit or NM type cable as appropriate.
Note: Acceptable wire is both solid core and stranded. Gauge range is 1.29 Ø[mm2]/1.31 Ø[mm2] -
0.511 Ø[mm2]/0.205 Ø[mm2]).
2.
Open appropriate terminals by depressing appropriate terminal buttons.
3.
Make connections to the appropriate ports.
Note: Wire strip length is 0.35-0.39 in (9-10 mm).
Refer to applicable protocol wiring diagrams.
V E R I F Y S U C C E S S F U L I N S TA L L AT I O N
1.
Apply power to circuit.
2.
Green "Power" LED will illuminate indicating successful installation and product functionality.
Optional: If data is present at any control port, appropriate LED will indicate status.
3.
4.
Disconnect power and install cover.
5.
Restore power and configure device using Ketra Design Studio Software.
6.
For software download and updates, visit www.ketra.com.
P/N 3662351 Rev B
© 2019 Ketra, Inc. All rights reserved.
(KetraNet systems only)
11 | N3 INSTALLATION GUIDE