4x0060 Scaling high - (10V)
Differential pressure sensor 2
4x0065 Reliability
4x0066 Value
4x0067 Unit
4x0068 Value [Pa]
4x0069 Value [PSI]
4x0070 Zero point calibration
4x0071 Sensor 2 full scale value
4x0072 Average 500 ms
4x0073 Average 1000 ms
4x0074 Average 4000 ms
4x0075 Average 16000 ms
Flow (Differential pressure sensor 1)
4x0081 Flow low
4x0082 Flow high
4x0083 k factor
4x0084 Unit
Flow (Differential pressure sensor 2)
4x0091 Flow low
4x0092 Flow high
4x0093 k factor
4x0094 Unit
Modbus Settings
4x0764 Modbus address
4x0765 Baudrate
4x0766 Format
4x0767 Modbus base address
4x0768 Bus config command
Supported function codes
Function codes
03 (0x03)
Read holding register
04 (0x04)
Read input registers
06 (0x06)
Write single register
16 (0x10)
Write multiple registers
24
mV
1
1
1
1
Pa
1
PSI
0.0001
1
Pa
1
see config #4x0067
see config #4x0067
see config #4x0067
see config #4x0067
0.01
0.01
1
1
0.01
0.01
1
1
1
1
1
1
1
Huba Control AG | Industriestrasse 17, 5436 Würenlos - 699M - Edition 02/2020 - 120225
Technische Änderungen vorbehalten | Technical data subject to change | Sous réserve de modifications techniques
R/W Scaling low < VAL (10000 = default)
R
See table "Fault correction"
R
R/W 0 = Pa = default
1 = PSI
2 = mmHG
3 = mmH2O
R
R
R/W 0 = no action
1 = zero point calibration P1+P2
2 = zero point calibration P2
3 = zero point reset to factory setting
P1+P2
4 = zero point reset to factory setting P2
R
R
R
R
R
R
R
R/W 0 ≤ VAL ≤ 1500
R/W 0 = m3/h = default
1 = m3/s
2 = l/s
R
R
R/W 0 ≤ VAL ≤ 1500
R/W 0 = m3/h = default
1 = m3/s
2 = l/s
R
1 ≤ VAL ≤ 247
R
0 = 9600
1 = 19200
2 = 38400
3 = 57600
R
0 = 1-8-E-1
1 = 1-8-O-1
2 = 1-8-N-1
3 = 1-8-N-2
R/W 1 ≤ VAL ≤ 247
40 = default
R/W 0 = ready = default
1 = load
2 = discard
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t