Room sensor AIR1/KWL-FTF 0-10V
EN
3.2 Electrical connection
In case of connection to an ventilation unit or fan, observe the wiring diagram, see the
installation and operating instructions for the ventilation unit or fan.
Fig.3
1
2
Output temperature 0-10 V in °C
-UB- GND
r. H.
°C
offset
Maximum cable length between sensor and controls: 50 m.
Recommended cable type for the sensor connection: shielded cable (provided by custo-
mer) with 0.5 mm² strand cross-section. The shield must be applied to the GND on the
control side.
85499-220 SS-1407 19.11.2020