4.2 Connection of electronically regulated circulating pumps
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary if
the permissible operating current of 2 A and a maximum starting
current of 12 A are not exceeded in the electronically regulated
circulating pump or if express approval has been issued by the
pump manufacturer.
ATTENTION!
It is not permitted to connect more than one electronically regulated
circulating pump via a relay output.
Load fuse for plug-in terminals J12; J13
F2
and J21 5x20 / 4.0 AT
Load fuse for plug-in terminals J15 to J18
F3
and J22 5x20 / 4.0 AT
F21 Fuse heat pump
N1
Controller
T1
Safety transformer 230 / 24 V AC
X1
Terminal strip infeed
X2
Terminal strip voltage = 230 V AC
X3
Terminal strip low voltage < 25 V AC
NOTE
Detailed connection diagrams can be found in the Appendix, Chap. 2.
NOTE
A communication cable must be laid between Econ5 and the heat pump.