 TYPICAL ARRANGEMENT FOR CONNECTION
Notice technique / Technical manual - ENCOD-USB – V1.0

3) INFX2 and OUTFX2 expansion modules (RS485)

Note:
You can connect:
Maximum 10 INFX2 modules to one C4PLUSFX
Maximum 10 OUTFX2 modules to one C4PLUSFX
(?)
Data sheet:
SYT recommended
Ø 0.6 mm
2 pairs recommended
12 V DC power supply
Relais 2
Relais 1
Ensure you use the same pair for A and B
Disconnect the power supply from the bus
RS485
Characteristic:
Sensitive connection
Screen:
Recommended
To achieve 1200m, you need to install a 220
resistor at each end of the network between
points A and B (see above).