Setting
RC. setting mode (Main/sub, Clock type, Password change)
Detailed settings (Vent output setting, Temp sensor setting, Temp display
setting)
1
Press and hold the 3 buttons for
4 seconds or more simultaneously.
,
, ►
2
Select the item to set.
▲ ▼ →
RC. setting mode
3
Set.
(Select the Code no. and Set data.)
▲ ▼ → ► →
(Repeat)
Code
no.
01
Main/sub
02
Clock type
Display of
36
operation lock
cancelling method
Password
2F
change
Detailed settings
3
Set.
(Select the indoor unit number, Code no. and Set data.)
▲ ▼ → ► →
(Repeat)
Code no.
Vent output
31
setting
Temp sensor
32
setting
Temp display
33
setting
12
(EN)
Set this when using 2 remote controllers.
Set the type of clock display.
Set whether to display the operation lock cancelling method on the
lock screen while operation is locked. (For the lock screen, see the
"Part Names" section in the Quick Reference.)
Set the administrator password.
Set this when connecting a commercially sold fan, etc. to the ventilation
fan output "FAN DRIVE:2P (White)" on the indoor control board.
*Dedicated cables (optional) are required.
Set this when measuring the room temperature with the room
temperature sensor of the remote controller.
• When using the main and sub controllers, the main one is enabled.
• When controlling in group, set this for the main indoor unit number.
(No setting is required for sub indoor units.)
• When using with the remote sensor in combination, set the indoor
unit setting data.
Set the type of temperature display.
Code no.
Set data
Set data
• 0000: Sub
• 0001: Main (factory
setting)
• 0000: 24 hours
• 0001: 12 hours (AM/PM)
• 0000: Displayed
(factory setting)
• 0001: Not displayed
• 0000 to 9999
• 0000 (factory setting)
Indoor unit
Set data
number
Code no.
Set data
• 0000: Not connected
• 0001: Connected
• 0000: Indoor unit
• 0001: RC
• 0000: °C
• 0001: °F