Several OXeN units controlled via single T-box
controller.Connection units among themselves ensure forwar-
ding controlling signals. However, each unit should be supplied
with power separately.
In case of chaining OXeN's (max. 31) - last unit in
line should has SW2 dipswitch in position T120. If
controlling only 1 OXeN SW2 dipswitch also has
to be in T120 position.
Recommended wires*:
OXeN –> OXeN min. – LIYCY 3x0,5mm
twisted pair A and B, max 50 m.
* Wires size should be chosen by the designer
Tbox controlling touch panel shows founded OXeN units. While
start up run search procedure.
NT 1704 B - 02/2018
Commande de plusieurs unités OXeN à l'aide
d'un seul contrôleur T-box. Le raccordement permet de
transmettre les signaux de commande à partir du contrôleur
T-box. Chaque unité OXeN doit être alimentée séparément en
électricité.
,
2
Câbles recommandés*:
OXeN –> OXeN min. – LIYCY 3 x 0,5 mm
paire de câbles A et B torsadée, max. 50 m
* Le type et le diamètre des câbles doivent être définis par l'auteur du projet.
Raccorder l'alimentation électrique et la commande, définir
l'adresse du dispositif, puis rechercher les unités OXeN dans le
menu du contrôleur Tbox.
En cas de plusieurs dispositifs (31 au maximum)
commandés par un seul contrôleur, dans le dernier
module DRV du dispositif auquel arrive le signal
de commande, le sélectionneur SW2 doit être
positionné sur T120. En cas d'un seul dispositif
commandé, le sélectionneur SW2 doit également
être positionné sur T120.
,