Electrical installation
Important notes
{
Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
Death or severe injuries when touching the device in the event of an error.
ƒ
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
Fixed installation
ƒ
– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section ³ 10 mm
Connection with a connector for industrial applications according to
ƒ
IEC 60309 (CEE):
– PE conductor cross−section ³ 2.5 mm
cable.
– Provide for suitable strain relief.
(
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
Destruction of the device if the mains voltage is too high.
ƒ
Protective measures:
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains fluctuations and
ƒ
voltage peaks.
50
2
as part of a multi−core supply
l
2
EDK94AZMS DE/EN/FR/ES/IT 8.0
.