Lights will not go into Low Mode:
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor's view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after 5
seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
Lights will not turn OFF:
• Cut Off time may be set to "Disable."
• Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor's view for that time period when
the lights are in Low Mode.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after 5
seconds and the OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks twice, the sensor has reached it's Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached it's Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks twice, the sensor has reached it's Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached it's Photocell Light Level setpoint.
There is no IR communication:
Perform a power cycle on the FSP-211B.
During the sensor warm-up period, which can last up to 5 seconds after initial power-up (or after a lengthy power outage), the load will
remain ON until the selected time delay expires.
Catalog #
FSP-211B
Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enlcosure
FSP-211B-S
Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enlcosure, with Straight Nipple Mount
FSP-211B-D
Single/ Dual Phase, PIR Fixture Integrated Sensor in IP66 Enlcosure, with Drop Nipple Mount
FSIR-100
Configuration Tool
FSP-L2
360° lens, up to 44' diameter at 8' height
FSP-L3
360° lens, up to 40' diameter at 20' height
FSP-L7
360° lens, up to 100' diameter at 40' height
Sensor colors indicated by one of the following suffixes at the end of the catalog #:
-W = White; -BL = Black; -BR = Bronze/Brown; -G = Grey/Silver
OPERATION DURING POWER-UP