In order to ensure maximal and durable service, we strongly recommend that your product be maintained clean
and ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages associated
with improper use or incorrect maintenance of the equipment.
WARNING
Replacing the battery with a battery of incorrect type may result in an explosion hazard.
Used batteries must be disposed of in compliance with recycling requirements.
If the AESI does not deliver voltage
Check mains presence on the mains terminal strip
Check the fuses
Check the voltage value on terminals load1 and/or load2
The voltage on the battery cables must be identical to that of the load
Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc
Repeat the measurement after having disconnected the load and the battery
Recheck the signalling of the indicator lights (see chapter 14)
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
Check the voltage on the battery terminals
Check the battery fuse
Check the voltage on terminals load1 and/or load2
If the indicator lights are not illuminated
Check mains presence on the mains terminal strip
Check the battery connection (and the battery fuse)
Check that the wire ribbon is properly connected
Check the voltage on terminals load1 and/or load2
For additional technical assistance, contact the SLAT hotline
For return requests, visit our website:
http://en.slat.fr/support-2/rma-customer-service/request-an-rma-number/
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation) number.
Returns are not accepted without an RMA number.
Primary fuse
User 1 fuse
User 2 fuse
Battery fuse
FBat
18 Troubleshooting procedure