General Information; Correspondence Table; Environmental Specifications; Electrical Characteristics - SLAT AESI C24 Notice D'utilisation

Masquer les pouces Voir aussi pour AESI C24:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

11.1 Correspondence table

24V
The currents (In) shown are at rated output power.

11.2 Environmental specifications

Operating temperature:
Operating maximum altitude:
Storage temperature:
Operating relative humidity:
Life time:
Pollution degree:
Overvoltage category:
Environment class:

11.3 Electrical Characteristics

11.3.1 Mains input
Single AC voltage: 115V - 240V
-
Frequency: 50 - 60Hz.
-
Class I.
-
Groundings: TT, TN, IT.
-
Double pole breaker C curve rated current between 2A and 10A to provide upstream.
-
Primary current @ 99V
Primary current @ 195V
11.3.2 Sortie
Nominal voltage
Output current In max.
Floating voltage (Un) at half load and
25°C
Current limitation – short circuit
current
Battery discharge current with no
mains and no load
HF peak-to-peak ripple (20MHz-50)
BF rms ripple
Static
and
dynamic
characteristics
Switching time
The AESI version can function without load current
The output current In max. can be used on a single outlet or distributed among
all outlets.
Maximum specified output current that can be supplied continuously while
charging the battery.
Maximum specified output current greater than I max a, that can be supplied for
a short period of time during which battery charging is not required.

11 General information

50W
- 10°C à + 40°C
2000m
-25 à + 85°C.
from 20 to 95%.
200 000 h @ 25°C (mains nominal @ 75% load housed)
II (according EN 60950)
II (according EN 60950)
1 (according to EN 12101-10)
III (according to VdS 2593)
24V
regulation
< 5% Un for total added mains and load variations (from 10 to 90%)
2A
50W
0.98A
0.52A
2A
27.2V
From In to In+15% for an output voltage > 50% Un.
38,5mA @ 24V
< 4% Un
< 0.2% Un
14
75W
3A
75W
1.50A
0.78A
24V
3A
+/-0.5%
0s
Imin = 0
In max.
See § 15.8
I max b = In max.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Aesi c38Aesi c85