Furman F1500-UPS E Manuel Du Propriétaire page 11

Masquer les pouces Voir aussi pour F1500-UPS E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 17
SWITCH OUTLET BANK
Turns a specific outlet bank ON or OFF. Switching is immediate with no delay.
Send to UPS: !SWITCH bank state<CR>
Where:
bank = {1, 2, 3, 4}
state = {ON, OFF}
Example: !SWITCH 2 ON<CR> (turns ON outlet bank 2)
If power to bank 1 or 2 is switched ON or OFF:
Action: Switch power to Outlet Bank 1 or 2
Response from UPS: $BANK 1 = state<CR>
or $BANK 2 = state<CR>
If power to bank 3 or 4 is switched AND battery level > Shutoff Threshold:
Action: Turn ON Outlet Bank 3 or 4
Response from UPS: $BANK 3 = ON<CR>
$BANK 4 = ON<CR>
If UPS battery level < Shutoff Threshold
Action: Turn off Outlet Bank 3 or 4
Response from UPS: $BANK 3 = OFF<CR>
$BANK 4 = OFF<CR>
$BATTERY = charge%<CR>
If entered bank or state are invalid
Response from UPS: $INVALID_PARAMETER<CR>
SET BANK 3 & 4 THRESHOLD
Sets the battery level threshold in which Outlet Bank 3 or 4 will shut off.
Send to UPS: !SET_BATTHRESH bank level<CR>
Where:
bank is the outlet bank to which the battery threshold is to be applied {3, 4}
Level is a number between 20 and 100 that represents the battery charge
level at which the selected outlet bank {3 or 4} is shut off to the reserve
remaining battery charge for the equipment connected to outlet Banks 1
and 2. The UPS will automatically round up the threshold argument to
the nearest interval of 10.
If level is >19 AND level <101
Action: SHUTOFF THRESHOLD will be set to a value between 20 and 100.
Response from UPS: $BTHRESH bank = level<CR>
If specified level is invalid
Action: No action will be taken, UPS will report INVALID_PARAMETER
Response from UPS: $INVALID_PARAMETER<CR>
SET BUZZER MODE
With Buzzer Mode ON, the buzzer will sound during UPS Mode.
Send to UPS: !SET_BUZZER mode<CR>
Where:
mode = {ON, OFF}
If specified mode is invalid
Action: No action will be taken, UPS will report INVALID_PARAMETER and
display current state of mode argument.
Response from UPS: $INVALID_PARAMETER<CR>
$BUZZER = mode<CR>
SET AVR MODE
Sets AVR (Automatic Voltage Regulation) MODE.
Send to UPS: !SET_AVR mode<CR>
Where:
mode = {OFF, STANDARD, SENSITIVE}
If specified mode is invalid
Action: No action will be taken, UPS will report INVALID_PARAMETER and
display current state of mode argument
Response from UPS: $INVALID_PARAMETER<CR>
$AVR = mode<CR>
SET FEEDBACK MODE
Sets the feedback mode to ON (unsolicited) or OFF (polled). When ON, a mes-
sage will be sent to the controller every time the status of an input (i.e. button),
output (i.e. outlet) or power state (i.e. overvoltage) changes. If feedback is OFF,
the controller must request status with a query (see Queries section for more
details).
Send to UPS: !SET_FEEDBACK mode<CR>
Where:
mode = {ON, OFF}
If specified mode is invalid
Action: No action will be taken, UPS will request a valid mode setting
Response from UPS: $INVALID_PARAMETER<CR>
$FEEDBACK = mode<CR>
SET LINEFEED MODE
With LINEFEED MODE set, a linefeed character (<LF>, 10d, 0Ah) will be
appended to each response.
Send to UPS: !SET_LINEFEED mode<CR>
Where:
mode = {ON, OFF}
If specified mode is invalid
Action: No action will be taken, UPS will report INVALID_PARAMETER and
display current state of mode argument.
Response from UPS: $INVALID_PARAMETER<CR>
$LINEFEED = mode<CR>
9

Publicité

Table des Matières
loading

Table des Matières