I N S T R U C T I O N S
Instructions Type AHC-3000
67783D 07/20 (PBV)
English
LIST OF FIGURES
The following figures are located at the back of the instructions:
Fig 1:
Dimensions, front and side view
Fig. 2a: Electrical terminal connections - AHC-3000-T
Fig. 2b: Electrical terminal connections - AHC-3000-B
Fig. 2c: Electrical terminal connections - AHC-3000-S
Fig. 2d: Connection overview
Fig 3:
External communication ports
Fig 4:
Internal communication ports
Fig 5:
Power supply connections
Fig 6:
Connection for HMI-35T
Fig 7:
Digital inputs
Fig 8:
Analogue inputs
Fig 9:
Cable for BMS Modbus connection
Fig 10:
Cable for BMS TCP/IP connection.
Fig 11:
Digital outputs 1-3
Fig 12:
Digital outputs 4-7
Fig 13:
Analogue outputs
Fig 14:
Connection of temperature sensors
Fig 15:
Connection as Building Master
Fig 15a: Shared outdoor temperature sensor
Fig 15b: Local outdoor temperature sensor
Fig 16:
Connection as Room Master
Fig 17:
Connection for Modbus cable
Fig 18:
Connection for Modbus cable
Fig 19:
Connection of DV fan drive
Fig. 20: Connection of Pressure transmitter, filters
Fig 20a: Connection of Pressure transmitter, flow
Fig 20b: Connection of Pressure transmitter, de-icing
INTRODUCTION
• Read this introduction thoroughly and follow the instructions it contains
before commissioning the AHC-3000.
• This introduction contains important information and should be used
when installing, connecting and commissioning the AHC-3000 as well as
during maintenance, servicing and troubleshooting.
• If the instructions contained in this introduction are not observed, the
liability of the supplier and the warranty no longer apply (see also Section.
Prohibition on use).
• Technical descriptions, drawings and figures may not be wholly or partly
copied or disclosed to third parties without the permission of the manu-
facturer.
• All rights are reserved if the product is included in patent rights or other
form of registration.
AIR HANDLING CONTROL 3000
AHC-3000 is an intelligent, configurable controller for an air handling unit
(AHU). AHC-3000 contains a preprogrammed range of applications, each
of which can be configured to ensure perfect adaptation to the ventilation
system concerned and the provision of precisely the functions needed for
energy-optimised control.
AHC-3000 handles all control functions, Modbus communication internally
in the AHU and remote communication to BMS and cloud.
AHC-3000 contains several different interfaces for peripheral units, allowing
it to be connected to fans, sensors, pumps and valves.
AHC-3000 can be connected to a BMS system via Modbus interface
Modbus RTU and Modbus TCP/IP. See models in Fig. 2
PRODUCT PROGRAMME
• English
Type
AHC-3000-S
• Deutsch
AHC-3000-T
• Français
AHC-3000-B
• Svenska
AHC-3000-HMI-35T AHC touch control panel 3,5 inch
• Norsk
OJ-Air2-HMI-20T
OJ Air Cloud
• Dansk
OJ-DV
• Русский
DRHX
OJ-Air2Ext
OJ-Zonemaster
PTH-6202
PTH-6202-2
HTH-6202
TTH-6040-W
TTH-6040-O
VTH-6202
ETF-598B-5
EFT-122
OJ Air PC Tool
OJ Air Service tool
CONFIGURATION
At the factory
The system designer configures the AHU specific settings in AHC-3000 at
the factory via the user-friendly OJ Air PC Tool or HMI-35T
Please see relevant manuals for further details. Settings are saved in
AHC-3000 as data files containing application and system parameters.
At the installation site
Once the system has been installed, it is tested and commissioned by a
technician, who sets energy-optimising and other user-specific parameters
on site using the AHC-3000-HMI-35T.
Please see the commissioning guide for further details.
Daily operation
Daily users operate the system via the AHC-3000-HMI-35T, OJ-Air2-HMI-
20T or OJ Air Cloud
Installation
AHC-3000 is designed to be mounted on a standard 35 mm DIN rail and
installed in a control panel or similar enclosure which complies with local
requirements for electrical installations (for dimensions, see Fig. 1).
The enclosure rating is IP20. Input and output signals to sensors and
actuators are connected to AHC-3000 by connectors equipped with screw
terminals.
Supply voltage
A 24 V AC or DC power supply must be connected from a 0.2 - 1.5 mm
screw terminal Ø45 (+24V) & Ø46 (G0) on AHC-3000.
G0 must be ground (GND) in order to use a single 24V AC transformer.
All G0 terminals are internally connected in the AHC-3000 and used as
GND for connected fans, sensors and valves. Electrical connections are
illustrated in Fig. 5
Connection of AHC 3000-HMI-35T
The AHC-3000-HMI-35T is connected to AHC-3000 via the RJ12 port
marked HMI on the front (see fig 6)
This HMI can be used simultaneously with OJ-Air2-HMI-20T if installed. If
a CAT5 cable is used, and a 120 ohm termination resistor is added at the
HMI-35T end, the length can be max. 100m.
© 2020 OJ Electronics A/S
Product
Controller for air handling unit, standard version
Controller for air handling unit, TCP/IP version
Controller for air handling unit, Bluetooth version
OJ-Air2 touch control panel 2 inch
Cloud service
®
OJ Drives designed for ventilation fans
Controller for rotary heat exchanger
I/O extension module
OJ GreenZone™ zone master
Pressure transmitter
Dual pressure and temperature transmitter
Duct humidity and temperature transmitter
Room temperature transmitter
Outdoor temperature transmitter
Duct VOC transmitter
PT-1000 temperature sensor
NTC 12k temperature sensor
PC tool available at www.ojelectronics.com
App for AHC-3000-B available at Google Play and
App Store
. Please see HMI/Cloud instructions for further details.
®
2