Product Information; Scope Of Delivery; Designated Use - Buderus S32/5 Notice D'installation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2

Product Information

2.1

Scope of delivery

• Tanks
• Tank drain (factory installed)
• Installation and Maintenance Instructions
• Compensation fields for aquastat or tank temperature sensor
• B-KIT
1
Fig. 1
B-kit
[1]
Tee ¾ " x ¾ " x ¾ "
[2]
Temperature and pressure relief valve
[3]
Coupling ¾ " (3x)
[4]
Holder for Aquastat, screws for Aquastat holder (2x)
2.2

Designated use

The tank is designed for heating and storing drinking water. Please
observe national, regional, and local codes, regulations, guidelines and
standards for drinking water.
Install this tank only in sealed unvented hydronic heating systems.
Any other purpose is considered improper use. Any resulting damage is
excluded from the manufacturer's warranty.
Requirements for drinking water
Water hardness, min.
pH value, min. – max.
Conductivity, min. – max.
Table 3 Requirements for drinking water
S32/5 – 6 720 819 302 (2017/11)
3
2
4
6 720 801 772-15.1T
Unit
ppm
36
grain/US gallon
2.1
°dH
2
6.5 – 9.5
μS/cm
130 – 1500
2
Product Information
5

Publicité

Chapitres

Table des Matières
loading

Table des Matières