3. Technical data:
In general:
Nominal voltages:
Number of digits:
Digit size (optical):
Digit color:
Temperature range:
Storage temperature:
Housing:
Protection type:
Connections:
Connections
(S0 outputs):
Energy meter:
Accuracy:
Current:
Current measuring range:
Initial current:
S0 output:
Standard:
Hour meter:
Accuracy:
S0 output:
HW66:
115/230 V AC, -20 % / +15 % 50 or 60 Hz
HW66M:
230 V AC, -20 % / +15 % 50 Hz
2 x 6 digits (units digit is red)
4 x 1.7 mm
white and red, background black
HW66: -20 °C to +55 °C; HW66M: -10 °C to +55 °C
-25 °C to +65 °C
DIN housing 48 x 48 mm for panel mount
installation depth 55 mm
IP 65, DIN 60529 from the front when mounted
Screw terminals, touch-proof
max. wire cross section: 2.5 mm
Screw terminals, touch-proof
max. wire cross section: 2.5 mm
Class B, (1%) acc. to EN05470 (for 50Hz version)
I max = 16 A
> 250 mA, 16 A
> 20 mA
1000 pulses/kWh, 5 ... 30 V DC, I max = 20 mA
EN50470-1 and EN50470-3
+ 2 %
10 Imp./h, 5 ... 30 V DC, I max = 20 mA
2
2
5