Télécharger Imprimer la page

VOGELZANG TR007 Manuel Du Propriétaire page 5

Publicité

LOCATING STOVE
1. The stove must be placed on solid concrete, solid masonry, or when installed on a combustible floor, on an
Underwriters Laboratories Listed Type 2 floor protector listed to UL standard UL 1618, such as Hy-C or Imperial
Model UL4056BK. Floor protector must be 1/2˝/13mm minimum thickness (R value = 1.19, K value = 0.84 see
page 23 for calculation formulas) non-combustible material or equivalent. The floor protector must extend
at least 18˝/46cm beyond the front of the access door, 8˝/21cm to the sides, 8˝/21cm beyond the rear and
must extend under and 2˝/50mm beyond either side of the stove pipe if it is elbowed towards a wall. (See
figures 4 – 6 and consult local building codes and fire protection ordinances.)
CAUTION: Fire hazard. Carpeting and other combustible material shall not cover the floor protector. These
materials must remain outside of combustible clearances, see fig. 5 – 7
2. The room in which the stove is installed must have a minimum floor to ceiling height of 8 ft. (2.4 m).
3. The stove must have its own flue. Do not connect this unit to a chimney flue serving other appliances. DO
NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
4. After observing the clearances to combustible materials (figures 4 – 6), locate your floor protector accordingly
(figure 4) and carefully place the stove in your selected location. Install connector pipe, elbows, and
thimble as required, utilizing either a recently cleaned and inspected 6˝/152mm lined masonry chimney or
a 6˝/152mm i.d. manufactured chimney system listed to UL 103 HT (US)/ULC-S629 (CDN).
5. Use round 6˝/152mm dia., minimum 24 MSG black or 26 MSG blue steel stove pipe to connect the stove
to the chimney. Do not use galvanized stove pipe. NOTE: Mobile home installations require double-wall UL
103 HT high-temp connector pipe. Secure connector pipe to the flue collar with three (3) equally spaced
sheet metal screws to firmly hold the pipe sections together. DO NOT CONNECT THIS STOVE TO ANY AIR
DISTRIBUTION OR DUCT SYSTEM.
6. Recheck clearances from the stove, connector stove pipe, and corner clearances using the illustrations in
figures 4 – 6 and your local building codes or fire protection ordinances.
NOTE: Any wall containing combustible material such as wooden studs or drywall and faced with brick or
7. NOTICE: for installation in a manufactured/ mobile home (USA only), please see specific requirements on
page 10.
8. The clearances provided are minimum dimensions set by US standard UL 1482-2011 & ULC-S627-00, tested
and applied by OMNI-Test Laboratories, Inc. the manufacturer's testing agency. Installation of this stove
must comply with the latest edition of NFPA 211 (US)/CAN/CSA-B365 (CDN) for reduced clearances and/or
your local building code rulings. Use whichever minimum dimensions are Clearances listed and shown MUST
be adhered to for safe operation of this appliance. CLEARANCES MAY NOT BE REDUCED BY ANY MEANS IN
USA OR CANADA.
9. This stove meets U.S. Test Standard: UL 1482- 2011& Canadian Standard: ULC-S627-00.
CAUTION: Keep furnishings and other combustible materials away from the stove.
NOTE: Before firing woodstove slide firebricks towards the rear so no gaps remain between bricks.
stone must be considered a combustible surface.
-5-

Publicité

loading