Input LEDs (Fig. 1):
You can choose between different operating modes, i.e. analog
control 0-10V, analog control 1-10V, 1-button mode or 2-button
mode (see 4. Programming). The input LEDs indicate which
operating mode has been selected.
In case of normal operation, the input LEDs can have the
following meaning:
LED's
Upper LED lights
continuously
Middle LED lights
continuously
Lower LED lights
continuously
None of the 3 LEDs
lights.
Troubleshooting
Possible causes if the error indication LED and the load LED blink:
- the lamp is defective
- the load is not connected
Possible causes of dimmer malfunction, no LED indication:
- no power on the mains
- there is no control signal
- thermal protection is activated
- combination of the above causes.
- The dimmer is provided with a thermal protection. If the
temperature rises too high, the light is automatically dimmed
to ±40%. If the temperature continues to rise, the dimmer is
switched off. If this happens:
- check whether the load is not too high. Take into account the
reactive power of ferromagnetic transformers.
- check the temperature in the distribution board (max. 35°C). If
the temperature is too high, provide additional ventilation.
- If several modules are installed next to each other, provide
min. 1 module distance via adapted blank plates.
The dimmer is automatically switched on again as soon as the
temperature has dropped suffi ciently.
- The error indication LED continuously blinks or lights. This
indicates:
- overload
- overvoltage or overcurrent
- short circuit
- the load is not dimmable, neither in phase control, nor in
reverse phase control.
Operation & maintenance
No maintenance.
Contact a qualifi ed electrician in the event of fault or breakdown.
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Meaning
Current operating mode: 0 -10 V
Current operating mode: 1 -10 V
Current operating mode:
1-button mode
Current operating mode:
2-button mode
Technical data
Input:
Power supply ......................... 230 V ±10%, 50 Hz
Maximum voltage drop
over dimmer .......................... -5%
Own consumption ................. ±1W
Input impedance:
0-10V .................................. 33k
1-10V .................................. 22k
Output:
Minimum load ........................ 60W
Maximum load ....................... 750VA resistive, inductive and
Max. output voltage .............. Supply voltage x 0.95 (dissipated
Protections ............................ Elektric, thermal protection (105°C)
Preformance:
Allowed ambient temperature .. see load table
Max. cover temperature (tc) ... 90°C
Maximum distance to last
push button ........................... 100m
Wiring of analog control:
Control circuit and power circuit of the dimmer are galvanically
isolated.
The control inputs of the dimmer comply with the
requirements for extra low safety voltage (SELV). If the control
signals originate from appliances that also meet the SELV
requirements, no specifi c requirements in terms of wire
diameter or insulation of the control wires apply. You do have to
keep the control wires apart from the 230V~ wires (min. 10mm).
In this is not the cases, the SELV guarantees do not apply.
Humidity ................................ Designed for use in an environment
Installation ............................. DIN rail (2U)
Weight ................................... ±144g
Max. wire diameter per connection terminal:
Power supply and load ...... 2 x 2,5mm
Input ................................... 2 x 2,5mm
Approval:
CE according to ..................... EN60669-2-1 and EN55015
Load table: power in function of ambient temperature
800
700
600
500
400
300
200
100
0
0
20
35
temperature (°C)
If the dimmers are placed next to each other, they can be loaded
for max. 80%.
capacitive(t°<35°C)
power = max. 1% of the absorbed
power = max. 7W)
with automatic rebooth function
(light is reduced to min. intensity). If
the temperature does not drop, the
load is switched off.
-single thermal overload protection
(135°C)
with a non-condensing atmospheric
humidity (30% - 70%)
2
2
or 1 x 4mm
2
or 1 x 4mm
2
50
GB
7(15)