VMF - E19I CONNECTIONS
• To install the VMF-E19I kit it is necessary to
replace the motor cable.
• Proceed with fixing the air probe (S.A.)
and the water probe (S.W.) (S.W.1 where
provided).
• Proceed with fixing the microswitch cable,
supplied.
• Connect the terminals provided to the
motor, respecting their polarization.
• Place the new motor cable through the
same slot in which the previous cable was
housed.
• Connect the two connectors of the new
motor cable in the housings CN21 and
CN22
• Connect the earth cable
• Make any connections with control panels
or network connections for Modbuss
communication.
• Close the box with the lid.
WARNING: Keep separate electrical
connections from water connec-
tions. Water connections and drain
should be on the side opposite of
the electrical connections.
42
AVMFE19LJ 2201 - 5779300_06
Installation for VMF-E19I only
Connection cable for VMF-E19I
CN22
CN21