AERMEC VMF-E19 Manuel D'utilisation Et D'installation page 35

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

There is a fixed correction of the ambient probe, defined on the basis of type of thermostat configured (see the ambient
probe corrections table).
No ambient probe (2 pipes)
In this case, the thermostat behaves as follows:
Selector on OFF - Aux
The valve is closed
The fan is switched off
Selector on AUTO, V1, V2, V3:
The valve is always open
Heating mode is always enabled
Ventilation follows On-Off cycles. The length of the ON cycle is proportional to the position of the temperature selector
(manual control of the power supplied by the terminal). The total length of the ON-OFF cycle is 5'20'' . The following table
shows examples of the duration of the various ON/OFF cycles according to the position of the temperature selector:
NO AMBIENT PROBE (4 PIPES)
In this case, the thermostat behaves as follows:
SELECTOR ON OFF - AUX:
The valves are closed
The fan is switched off
SELECTOR ON AUTO, V1, V2, V3:
The operating season is defined according to the position of the temperature selector, activating the relative valve as
shown below:
Opening of the cooling valve - ventilation period
proportional to the average pressure deviation
In this case, ventilation follows ON-OFF cycles but the ON phase is increased from the central position upwards. This
means maximum ventilation can be requested with the selector on the minimum position for cooling mode, and with the
selector on the maximum position for heating mode. The total length of the ON-OFF cycle remains 5'20'' . The following
table shows examples of the duration of the various ON/OFF cycles according to the position of the temperature selector:
NO AMBIENT PROBE (2 PIPES FOR COOLING + HEATER FOR HEATING)
In this case, the thermostat behaves as follows:
SELECTOR ON OFF:
The valves are closed
The fan is switched off
SELECTOR ON AUTO, V1, V2, V3, AUX:
The operating season is defined according to the position of the temperature selector, activating the coil valve for
cooling mode or the heater for heating mode:
Opening of the valve in cooling mode and enabling of V1
Position
ON cycle duration
Min.
Central
Max.
Set value selector
Position
ON cycle duration
Min.
Central
Max.
Set value selector
OFF cycle dura-
tion
0
5'20"
2'60"
2'60"
5'20"
0
Opening of the heating valve - ventilation period
proportional to the average pressure deviation
OFF cycle dura-
tion
5'20"
0
0
5'20"
5'20"
0
Activation of the heater and enabling of V1
AVMFE19LJ 2201 - 5779300_06
35

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vmf-e19iVmf-e19i7

Table des Matières