Component location
Battery connector
Control cable connector
Control
terminal
Earth
terminal
ATTENTION: Make sure to turn of the equipment's power supply before handling it, as different areas
may be energised.
IMPORTANT: The availability of the elements described depends on the panel model.
Technical specifications
Rated voltage Un ...................................................................................................................................400 V~ ±10 % 50 Hz ±5 %
Rated voltage Ue....................................................................................................................................230 V~ ±10 % 50 Hz ±5 %
ALARM relay.................................................................................................................................................... 8A at 250V, cosj=1
Probe temperature range....................................................................................................................................–40.0 ºC to 99.9 ºC
Resolution, setting and differential .........................................................................................................................................0.1 ºC
Thermometric precision .........................................................................................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC......................................................................................................................................± 0.4 ºC
Input for NTC probe ......................................................................................................................................................AKO-14901
Maximum input power in the operation ...................................................................................................................................30 VA
Working ambient temperature.....................................................................................................................................-5 ºC to 40 ºC
Storage ambient temperature ...................................................................................................................................–30 ºC to 70 ºC
Overvoltage category..............................................................................................................................................II s/ EN 61439-1
Degree of pollution .................................................................................................................................................II s/ EN 61439-1
Degree of protection ................................................................................................................................................................IP65
Dimensions ......................................................................................................................................400(An) x 300(Al) x 135(P) mm
Double isolation between power supply, secondary circuit and relay output.
Logger battery life if the power supply fails ..........................................................................................................................48 hours
Battery............................................................................................................................................................Li-Polymer for logger
Type of assembly ........................................................................................................................................................Fixed internal
Internal buzzer
Encapsulated assembly
Probe and communications terminal
18
1565H051 Ed.01
Protections
Phase detector
Contactors
Insulation
transformer
Power supply
terminal