Technical Data - JUMO di eco Notice De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Technical data

Meas. input
Designation
RTD tempe-
Pt100 EN 60 751
rature probe
Pt1000 EN 60 751
KTY2X-6 (PTC)
resistance 0 to 3000 Ω
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 or resistance: 0.02 mA
Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance (sensor+lead) must not exceed 320Ω with Pt100 and 3200Ω with Pt1000, KTY2X-6 or
resistance.
Thermo-
Fe-Con J EN 60 584
couple
Fe-Con L DIN 43710
NiCr-Ni K EN 60 584
-10 to +60 mV
For the voltage input (-10 to 60 mV), terminal temperature compensation for thermocouples can be used.
Internal terminal temperature compensation can be switched off through the setup program (0°C).
Meas. range
Meas. accuracy
ambient
temperature error
0.1%/ ≤100ppm/°C
-200 to +600°C
0.1%/ ≤100ppm/°C
-200 to +600°C
1%/ ≤100ppm/°C
-50 to +150 °C
3
0.1%/ ≤100ppm/°C
customer table
0.4%/ ≤100ppm/°C
-200 to +999 °C
0.4%/ ≤100ppm/°C
-200 to +900 °C
0.4%/ ≤100ppm/°C
-200 to +999 °C
0.1%/ ≤100ppm/°C
3
customer table
1
/
Recognition of ...
Probe short-
Probe break
circuit
recognized
recognized
recognized
recognized
recognized
recognized
3
= 0Ω
recognized
2
-
recognized
2
-
recognized
2
-
recognized
3
-
recognized
17

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

B 701540.0

Table des Matières