Valor 720SWK-M Guide D'installation page 2

Sortie d'évacuation colinéaire murale

Publicité

Les langues disponibles

Les langues disponibles

739M & 739V fireplaces
720SWK-M
720SWK
Terminal
Terminal
Min. 3'-0"
*Max. 10'-0"
* If more than 10'-0" vertical
vent run, the vent plate
supplied on the appliance (with
restrictor) can be used. No
need to replace it.
739MN/MP & 739VN/VP
MODELS
This procedure must be done before
installing the appliance into the
masonry cavity.
The 739MN/MP and 739VN/VP
appliances are supplied with the
AutoFire vent collar slider plate
having an integral restrictor built-in.
When using the 720SWK-M Sidewall
Kit, the vent collar slider plate must
be replaced with one having no
restrictor (see instructions below).
The 739MN/MP and 739VN/VP do
not have restrictor plates behind the
rear log as other 739 models do.
1. Remove the existing vent slider
plate having built-in restrictor.
2. Replace with a vent slider plate
having no restrictor supplied
in this kit. (If more than 10'-0"
vertical vent run, vent plate with
restrictor can remain in place).
3" min.
Bend
Radius
Vent plate with restrictor
Vent plate without restrictor
(no. 4001133) Supplied
(use when less than 10'-0"
vertical vent run)
3" Liners