HEATER ELEMENT CHANGE
When a faulty heater element is found, it must be replaced as soon as possible.
If the star point is not connected, there is a risk of a knock-on effect in which the other heaters will also break down.
This operation can only be undertaken once the electrical supply has been switched off (consignation).
Remove the defective heater and clip in the new heater.
6- TROUBLESHOOTING
Examples of faults
FAULT
Evaporation Pressure too low
M a n u f a c t u r e d in F ra n c e by P R O F R O I D C A R RI E R S. C. S
178, rue du Fauge - ZI Les Paluds - B.P. 1152 - 13782 Aubagne Cedex - France
PROBABLE CAUSE
Insufficient flow air flow.
Insufficient liquid in installation.
Superheat too great
Thermostatic expansion valve:
Work above MOP point.
Pressure regulator not connected
International: Tel. (33) 4 42 18 05 00 - Fax (33) 4 42 18 05 02
ACTION REQUIRED
Coil iced up
Add remainder of charge.
Check and adjust the expansion valve
Change or adjust expansion valve