Gas Supply Pressure; Gas Connection - Amana AKGD3050 Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Gas Supply Pressure

!
CAUTION
To avoid property damage, maximum gas supply
pressure must not exceed 14" WCP.
• Appliance and individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures higher than ½ psig (3.5kPa)(14" WCP).
• Appliance must be isolated from gas supply piping
system by closing manual shutoff valve during any
pressure testing of the gas supply piping system at
test pressures equal to or less than ½ psig (3.5kPa)
(14" WCP).
• Gas supply pressure for checking regulator setting
must be at least 1" WCP above manifold pressure
shown on rating label.
• Must use pressure regulator supplied with cooktop.

Gas Connection

!
WARNING
To avoid property damage or personal injury, only
use a new flexible connector that is AGA/CGA
design certified.
• Do not use an old connector.
• Do not reuse a connector after moving
appliance.
!
WARNING
To avoid property damage or personal injury, do not
use LP/propane gas to fuel this cooktop. Cooktop is
not convertible to LP/propane gas.
Connect gas supply to regulator using hard pipe or a
flexible connector. Pressure regulator supplied with this
appliance has a ½-inch NPT female connection.
• A manual shutoff, not supplied with cooktop, must be
installed in an accessible location outside of cooktop.
• Use joint compound that is resistant to action of
propane gas on all male pipe threads.
• Use supplied pressure regulator only.
• Do not overtighten gas fitting when attaching to
pressure regulator. Overtightening may crack
regulator.
• Support pressure regulator with wrench when
installing gas fitting.
• Refer to National Fuel Gas Code or local codes for
supply pipe size requirements to assure sufficient gas
supply to unit.
A—Regulator
B—Adaptor
C—Flexible Connector
D—Manual Shut Off Valve
Typical Flexible Connection
F
A—Union
B—Manual Shut Off Valve
C—Reducing Elbow (3/4-inch to 1/2-inch)
D—3/4-inch Stub
E—1/2-inch Nipple
F—Regulator
Typical Hardpipe Connection
12
A
B
C
D
A
B
C
E
D

Publicité

Chapitres

Table des Matières
loading

Table des Matières