DESCRIPTION
4
5
8
Target DeltaT for modulation
5
ZONE 2 PARAMETERS (if present)
5
0
Temperature setting
5
0
0
Daytime temperature
5
0
1
Night-time temperature
5
0
2
Zone 2 temperature
5
0
3
Zone anti-frost temperature
5
1
Automatic summer/winter function
5
1
0
Activating auto summer/winter
5
1
1
Auto summer/winter temperature limit
5
1
2
Summer/winter switching delay
5
2
Zone 2 settings
5
2
0
Temperature range
5
2
1
Temperature adjustment type selection
5
2
2
Temperature adjustment curve
5
2
3
Parallel shifting
5
2
4
Proportional room influence
5
2
5
Max T
5
2
6
Min T
5
2
9
Heat request mode
5
3
Zone 2 diagnostics
5
3
0
Room temperature
RANGE
[-5; -20°C]
10 - 30 °C
10 - 30 °C
par. 5.2.5 - 5.2.6
2 - 15 °C
OFF - ON
10 - 30 °C
[0-600]
Low temperature
High temperature
Fixed delivery temperature
Devices ON/OFF
Room sensor only
Outdoor sensor only
Room Sensor + Outdoor Sensor
0.2°C - 1°C (LT); 1°C - 3.5°C (HT)
-14 - +14 (HT); -7 - +7 (LT)
0°C - 20°C
20°C - 45°C (LT); 20°C - 70°C (HT)
20°C - 45°C (LT); 20°C - 70°C (HT)
Standard
RT Time Programs Exclusion
Heat request forcing
EN - 41