Custom Energy Savings Settings
13 – MINIMUM SETBACK TEMPERATURE - HEAT
(52°F - 72°F; 65°F* default setting) Select the "Minimum
Setback Temperature" in °F.
Setback temperature is calculated by measuring HVAC
unit's ability to attain "Recovery Temperature - Heat"
within "Temperature Recovery Time".
If recovery is disabled ("Temperature Recovery Time" is
set to "0") or if setback temperatures have not yet been
calculated, the "Minimum Setback Temperature" value will
be used as the setback temperature for heating.
If calculated setback temperature for heating is lower
than "Minimum Setback Temperature", then the
"Minimum Setback Temperature" will be used as setback
temperature for heating.
This feature allows defining the minimum temperature in
a room when room is unoccupied and the thermostat is in
the setback mode.
33
49-5000416 Rev. 1