User guide
Luxstat Control Box 77-050
General
Operation
The Luxstat Dim unit consists of an integral unit containing 1-10 V
control, a potential-free relay and an integral IR receiver. All
external units, such as motion sensors, low-voltage pushbutton
switches, light sensors and light fi ttings are connected directly to
the Luxstat Dim unit, which can be wall-mounted in the room.
If the Luxstat Dim unit is installed above a suspended ceiling,
it can be connected to an external IR receiver (optional) via an
RJ12 plug so that an IR remote control can be used.
The Luxstat Dim unit can be installed and operated using the
factory settings.
However, for optimal control it is recommended that you adjust
the settings for the Luxstat Dim unit for the room in which it is to
be used (light conditions). This is done via the IR-remote control
unit, type 77-920 (accessory).
Installation
Installation:
The Luxstat DIM unit is designed to be mounted directly on a wall.
Remove the outer cover by loosening the two securing screws
and lift off the cover, see Fig. 1
Connections:
See connection diagram, Fig. 2.
For App. Class see also Fig. 3B
For App. Man and App. Auto see also Fig. 3A and/or Fig. 3B
The Dim output must be installed as a high voltage installation
Glossary
App. Class:
Application for classroom with blackboard light, manual on and off via
pushbutton switch, automatic off via movement sensor, or daylight.
App. Man:
Application manual, manual on and off via pushbutton switch,
automatic off via movement sensor, or daylight.
App. Auto:
Application automatic, automatic on and off via movement
sensor, daylight-dependent.
Lux 1 indoors:
Current light level (lux) at selected reference point (table height)
in zone 1
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Lux 2 indoors:
Current light level (lux) at selected reference point (table height)
in zone 2
LS:
Manual setting of light sensor value
Setpoint 1:
Desired light level (lux) at table height in zone 1
Setpoint 2:
Desired light level (lux) at table height in zone 2
Off delay:
Cut-off time before motion sensor switches off the light
Cut off:
Cuts off 230 V power supply to HF ballast
Vout min / Vout max:
Option for limiting the 1-10 V control signal, e.g. to 2-8 V
Daylight factor:
This describes the amount of daylight falling into a room.
Technical data
Input:
Supply voltage .................................. 230 V AC 50 Hz ±10%
Power consumption ......................... <1 W
Output:
Relay Ch 1 and Ch 2 ........................ NO, µ 10 A
Load:
Incandescent lamps ..................... 2,300 W
Fluorescent tubes, not
compensated ............................... 1200 VA
Halogen incandescent lamps ....... 2300 W
Energy-saving bulbs ..................... 58 pcs (18 W)
Max. compensation capacity .......... 140 µF
Max. inrush current ......................... 165 A / 20 m sec.
Relay On/Off Ch 3 ............................ NO, µ 10 A, potential-free
Load:
Incandescent lamps ..................... 2,300 W
Fluorescent tubes,
not compensated ......................... 1200 VA
Halogen incandescent lamps ....... 2,300 W
Energy-saving bulbs ..................... 58 pcs (18 W)
Max. compensation capacity .......... 140 µF
Max. inrush current ......................... 165 A / 20 m sec.
Secondary voltage ........................... 24 V DC ±10%
Max. load .......................................... 100 mA
Performance:
Ch 1 + 2 Dim .................................... 1-10 V/max. 10 mA
Time range (Off delay) ...................... 1-60 min
Lux range:
Light sensor .................................. 30-3000 Lux
Indoor ............................................ 50-1000 Lux
Setpoint ......................................... 50-1500 Lux
Enclosure class ................................ IP 20
Insulation class:
Dim output .................................... Cl I
Sensor and switch connection...... Cl II
Ambient temp. .................................. -5°C to +50°C.
Approval:
CE pursuant to ................................. EN 60669-2-1
Accessories
PIR Sensor ....................................... 24 V DC
Light sensor ...................................... Model 43-197
Switch (1 or 2 pcs.) ........................... Model 74-593
External IR Sensor ............................ Model 77-910
IR Remote (remote control) .............. Model 77-920
77Y050_03_R6_090217KOE
77Y050_03_R6_090217KOE
GB