Confi guration
Settable parameters:
- Running pressure.
When the pressure in the
system falls below the Pm,
PRESFLO
starts-up the pump.
®
The Pm should always be
higher by at least 0.2 – 0.3
bar of the pressure genera-
ted by the column of water
overlooking PRESFLO
.
®
The Pm value can be carried
in the fi eld between 1 bar and
5 bar.
- Maximum current
allowed.
PRESFLO
is fi tted with a cur-
®
rent sensor, which continually
detects the absorption of the
pump. If the current remains
above the set Imax value for
a signifi cant period of time,
PRESFLO
stops the pump to
®
protect it from damages (LOCK
condition for OVERCURRENT).
PRESFLO
nevertheless allows
®
the Imax to be exceeded for
short periods during the pump
start-up phase.
For correct functioning,
the Imax should be set at
a value higher by approx.
10 – 20% to the maximum
absorption of the pump
(normally indicated on the
rating plate of the motor).
If this rating value is not known,
it s better to leave the standard
Imax value (16A) to avoid that
the pump stops also in normal
absorption conditions.
The Imax value may be varied
in the fi eld between 4A and
16A.
Disposal
When disposing of any
PRESFLO
parts, adhere
®
to the relevant laws and
regulations in force in the
country in which the equip-
ment is being used.
Do not dispose of
any polluting parts
in the environment.
Manufacturer's setting:
PRESFLO
is supplied with the
®
following STANDARD CONFIGU-
RATION:
- Running pressure
Pm = 2 ( bar )
- Max. current allowed
I max = 16 ( A )
Confi guration
The adjustment of the starting
pressure (Pm) and the ma-
ximum permissible current (I
max) is done by means of two
trimmers shown in FIG.
Statement of Compliance: we declare, under our own responsi-
bility, that the product in question is in compliance with the follow-
ing European Directives and national implementation provisions
2014/35/CE, 2011/65/CE,
2012/19/CE, 2003/108/CEE,
2014/30/CE,
EN 60730-2-6, EN 61000 6-3
UK legislation:
2016 No. 1101, 2012 No. 3032,
2016 No. 1091
1. Remove the small screwdri-
ver and adjust the trimmer on
the desired limits, according to
the values shown on the plate
located under the screwdriver.
2. The start-up pressure can
be adjusted continuously from
1 to 5 bar (trimmer A)
San Bonifacio 01/07/21
PEDROLLO S.p.A.
Il Presidente
Silvano Pedrollo
Silvano Pedrollo
3. The maximum permissible
current can be adjusted
continuously from 4 to 16 A
(trimmer B)
4. When you fi nish adjustment
close the cover