Basic settings
Para-
Function
meter
S1.1
HYDRAULIC SCHEME
S1.2
CODE FOR UNLOCKING
THE SERVICE SETTINGS
S1.3
TEMPERATURE SENSOR
TYPE
S1.4
ACTUATOR OPENING
DIRECTION
S1.5
DISPLAY ORIENTATION
S1.6
SELECTION OF SENSOR T1
FUNCTION
S1.7
SELECTION OF SENSOR T4
FUNCTION
S1.8
REMOTE ACTIVATION
VIA BUS
S1.9
ANTI-BLOCK FUNCTION
FOR PUMP AND VALVE
S1.10 BUILDING TYPE (TIME
CONSTANT)
S1.17 SENSOR T1 CALIBRATION Correction of displayed measured temperature for sensor T1.
S1.18 SENSOR T2 CALIBRATION Correction of displayed measured temperature for sensor T2.
S1.19 SENSOR T3 CALIBRATION Correction of displayed measured temperature for sensor T3.
S1.20 SENSOR T4 CALIBRATION Correction of displayed measured temperature for sensor T4.
Settings for heating circuit
Para-
Function
meter
S2.1
INFLUENCE OF ROOM
TEMPERAT. DEVIATION
S2.2
INFLUENCE OF ROOM
SENSOR T1
:
Parameter description
Selection of hydraulic scheme.
This setting enables the change of code which is necessary to
unlock the service settings.
WARNING! Keep new code on a safe place. Without this code
is impossible to change service settings.
Selection of temperature sensors Pt1000 or KTY10.
Setting of actuator turning direction - valve opening.
Setting of display orientation.
Set the operation mode for sensor T1.
If return pipe sensor is selected, a limitation of temprature
difference between stand and return pipe needs to be set with
parameter S2.13.
Set the operation mode for sensor T4.
If return pipe sensor is selected, a limitation of temprature
difference between stand and return pipe needs to be set with
parameter S2.13.
Selection if remote activation can be activated only local or
also from master controller.
All outputs that haven't been activated in the last week are
activated on Friday at 20:00 for 60 seconds.
Selection of building type (time constant). For heavy (thick
walls ) and good isolated buildings select higher value. For
light (thin walls, no heat accumulation) and poor isolated
objects select lower value.
:
Parameter description
Set the value of gain of room temperature deviation. Lower
value means lower influence, higher value means higher
influence.
Set whether the room sensor influences the controller operati-
on. This function is active only if parameter S1.6=0 (room
sensor).
33
Setting range
Default
value
360 ÷ 360b
360
0000 ÷ 9999
0001
0 - PT1000
0
1 - KTY10
0- RIGHT
0
1- LEFT
0 - REGULAR 0°
1 - ROTATED
0
180°
0- ROOM
SENSOR
0
1- RETURN PIPE
SENSOR
0- BOILER
SENSOR
0
1- RETURN PIPE
SENSOR
1- LOCALY
2- FROM MAS-
1
TER
0- OFF
0
1- ON
0 ÷ 12 h
6
-5 ÷ 5 K
0
-5 ÷ 5 K
0
-5 ÷ 5 K
0
-5 ÷ 5 K
0
Setting range
Default
value
1
0,0 ÷ 3,0
1- YES
1
2- NO
Service settings manual